PMC96S meter is a multi-functional power monitoring meter, it combines function of collecting data and control, and it can replace many kind of meters, relays, transformers and others components. PMC96S can be installed in different positions of electricity distribution system.
Product Description
Host features
Instantaneous true RMS value
Current each single phase and conjunction, average
Phase voltage/line voltage each single phase and conjunction, average
Active, reactive, apparent power each phase and the sum of three phases
Power factor each phase and the sum of three phases
Frequency 45~65Hz
Maximum/minimum value
Max/min rms current
Max/min rms phase voltage
Max/min total active, reactive, apparent power
Max/min total power factor
Max/min frequency
Max/min THD I and THD U
Demand and peak demand value
Current per phase current value/peak/month end peak
Total active, total reactive, total apparent power current value/peak/month end peak
Energy
Input/output/total active energy 1 pulse output
Input/output/total reactive energy 1 pulse output
Apparent electrical energy
Monthly electrical energy
Compound rate of electrical energy
8 multi-rated periods, 4 rates can be set
Power quality
Total Harmonic Distortion Rate (THD) current and voltage
1st-31st harmonic analysis current and voltage
Voltage crest factor CF and current K coefficient
Event logging
100 SOE event records
Alarm system
8 configurable limit alarm channels
4 configurable logical alarm channels
Communication
RS-485 /MODBUS-RTU Protocol
Display
STN LCD display
Real-time clock
Year, month, day, minute, second
Other
Program online upgrade supported
Optional features
Digital Input (DI) module (optional)
2 switching inputs
Digital Output (DO) module (optional)
2 relay outputs, which can be set by local overrun alarm or controlled remotely
Analog Input (AI)/Output (AO) module (optional)
2 channels. 4-20mA DC analog input, 0-5V DC analog input, 4-20mA DC analog output optional.
Product Parameters
Electrical characteristics
System
Three-phase three-wire AC system, three-phase four-wire AC system;
Sample rate
128 samples per cycle
Data refresh rate
1s
Measurement accuracy
Current
±0.2%FS
Voltage
±0.2%FS
Power
0.5S
Frequency
±0.001Hz
Active energy
0.5S
Reactive energy
1.0S
DC input (AI)
0.5% FS
DC output (AO)
0.5% FS
Voltage input
Measure voltage
3*220/380V (Direct input)
3*57.7/100V (PT secondary)
Overload
1.2x/continuous
Input impedance
300KΩ per phase
Current input
Measure current
5A (CT secondary) or 1A (CT secondary)
Overload
1.2x/continuous
Input impedance
<0.1Ω
Digital input
Operating voltage
15 VDC
Input impedance
12 KΩ
Isolation voltage
2 KV
Digital output
Node type
Mechanical contacts
Node capacity
220 VAC/5A,30 VDC/5A
4~20mA DC input measurement
Measure current
4~20mA
Allowed overload capacity
1.2x/continuous
Input impedance
10 Ω
Isolation voltage
2 KV
0~5 V DC input measurement
Measure voltage
0~5 V
Allowed overload capacity
1.2x/continuous
Input impedance
12.5 KΩ
Isolation voltage
2 KV
4~20mA DC output
Open-circuit voltage
15 VDC
Load capacity
≤600 Ω
Isolation voltage
2 KV
Working power supply
AC
100~240 VAC/45~65Hz
DC
100~375 VDC
power consumption
< 3 W
Mechanical characteristic
Weight
0.5 kg
IP protection rating
Instrument panel IP52, instrument body IP30
Size
host
96 *96 * 72 mm
Host + module
96 * 96 * 120 mm
Operating temperature
display
-20~70°C
Instrument
-25~70°C
Storage temperature
instrument + display
-40~85°C
Humidity
5% ~ 90%RH, non-condensing
Electromagnetic compatibility
Electrostatic discharge
IEC 61000-4-2, L