• Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
  • Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
  • Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
  • Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
  • Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
  • Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker

Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker

Breaking Capacity: High Voltage Circuit Breakers
Operation: Manual Type and Energy-Storage Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Vacuum
Installation: Fixed
Structure: Vcb
Customization:

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
ZW8-12 (G)
Type
Circuit Breaker
Function
Break Load Current, Over-Load Current
Certification
ISO9001-2000
Altitude
<1000m
Ambient Temperature
-40oc ~ +45oc
Wind Speed
34m/S
Wind Pressure
700PA
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year

Product Description

PHOTOS OF PRODUCT

GENERAL
 
ZW8-12 (G) series outdoor high-voltage AC intelligent vacuum circuit breaker (hereinafter referred to as "circuit breaker only") is applicable to the three-phase power system with three-phase AC 50Hz and voltage of 12kV. It is used for breaking and closing load currents. It has overload and short-circuit protection, definite time-delay protection, and an automatic reclosing function, and can also be equipped with a lightning arrester or isolating switch according to user needs.

The intelligent circuit breaker meets the requirements of GB / T 1984-2014 high voltage AC circuit breaker, DL / T 402-2016 high voltage AC circuit breaker, and DL / T 403-2000 technical conditions for ordering 12kV ~ 40.5kV high voltage vacuum circuit breaker and DL / T 721-2013 remote terminal of the distribution automation system.

MODEL DESCRIPTION

Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
USAGE: ENVIRONMENTAL CONDITION
  1. Altitude:  1000m, If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.
  2. Ambient temperature: -40oC ~ +45oC, 
  3. Maximum daily temperature difference: 25K 
  4. Humidity: Average daily relative humidity: 95%, average monthly relative humidity: 90%. 
  5. Sunshine intensity: not more than 0.1W/cm2 
  6. Wind Speed:  34m/s 
  7. Wind pressure: 700Pa
  8. Pollution level: e - level
  9. Icing thickness: Not more than 10mm 
  10. Resistance to floor drain: horizontal acceleration 0.3g, vertical acceleration 0.2g
MAIN ADVANTAGES

☆ Ceramic vacuum arc extinguishing chamber is adopted, with strong arc extinguishing ability and short-circuit breaking ability;
☆ It has the advantages of being explosion-proof, anti-condensation, anti-pollution, and no environmental impact
☆Air silicone rubber and engineering plastic composite insulation are adopted to avoid the possibility of insulation accidents caused by oil deterioration in oil insulation;
☆ The body can be equipped with an isolating switch to form a "combined electrical apparatus" with obvious fracture. The user can choose to use a silicone rubber insulating sheath on the isolating switch. The sheath has the advantages of rain, snow, sand, and strong resistance to pollution and corrosion, which can effectively improve the anti-freezing and anti-oxidation ability of the isolating switch;
☆ It can realize three-stage protection, zero sequence grounding protection, reclosing, and remote communication.

MAIN TECHNICAL PARAMETERS
 
No. Item Unit Data
1 Rated frequency Hz 50
2 Rated voltage kV 12
3 Rated current A 630 / 1250
4
Rated short-time power frequency withstand voltage
Interphase, to earth(wet) kV/min 34/1
Interphase, to earth(dry) 42/1
Fracture (dry) 48/1
Secondary circuit to earth 2/1
5 Rated lightning impulse withstand voltage Interphase, to earth kV 75
Fracture 85
6 Rated short-time withstand current and duration kA/s 20/4   25/4
7 Rated Short-circuit breaking current(Effective value) kA 20 / 25
8 Rated short-circuit making current(peak) 50 / 63
9 Rated Peak-withstand current 50 / 63
10 Main circuit resistance Without Isolation Switch μΩ not less than 120
With Isolation Switch not less than 200
11 Rated Short-circuit breaking current breaking times Times 30
12 Rated operating voltage and Rated Voltage for auxiliary(control) circuit V AC/DC220
DC48, DC24
13 Mechanical life Times 10000 
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.

OUTLINE AND INSTALLATION DIMENSION
Zw8 Series Outdoor High - Voltage AC Intelligent Load Switch Vacuum Circuit Breaker
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

360° Virtual Tour

Diamond Member Since 2019

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
302
Year of Establishment
1996-09-15