Breaking Capacity: High Voltage Circuit Breakers
Operation: Energy-storage Type
Arc-extinguishing Medium: Vacuum
Type: Circuit Breaker
Certification: ISO9001-2000
Transport Package: Plywood Case
Customization:
Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
  • Overview
  • Product Description
Overview

Basic Info.

Model NO.
ZW50-40.5
Trademark
JOYELECTRIC
Origin
China
HS Code
85352100

Product Description

ZW50-40.5 Outdoor Three-phase AC High Voltage Vacuum Circuit Breaker

1.ZW50 outdoor three-phase AC high voltage vacuum circuit breaker
2.It is applicable to the feeder side of substation and the industrial and mining enterprise which need general protection, control and frequent operation of switch.
3.Simple structure, powerful interrupting capability and long service life
 

Product Description

 

ZW50 outdoor three-phase AC high voltage vacuum circuit breaker (hereinafter as "vacuum(circuit)breaker ") is an outdoor distribution unit of rated voltage 40.5 kV and frequency 50 Hz, which is applicable to the feeder side of substation and the industrial and mining enterprise which need general protection, control and frequent operation of switch.
The main body of the circuit breaker features vacuum extinction, simple structure, powerful interrupting capability and long service life. The pole is made of epoxy resin / silicone rubber composite insulator,no oil and sf6 gas, this solid insulated Vacuum Circuit Breaker is designed envirionmentally friendly.


Application Ambient Condition
Ambient temperature: max. + 40ºC, min. -40ºC;
Altitude above sea level: not higher than 2000 m;
Wind pressure: not higher than 700 Pa (equivalent to wind speed 34 m/s)
Ice coating thickness: 10 mm
Air pollution grade: Class IV;
Earthquake intensity: not exceed 8 degree;
No flammable, explosive, corrosive chemicals (such as acid, alkali and dark smoke) and strong vibration on the site
 
Technical Parameters

No. Item Unit Value
1 Rated voltage kV 40.5
2 Rated insulation level (Sea level: 1000m) 1 min power frequency withstand voltage Dry test 95
Wet test (earth outside insulation) 85
Lightning impulse withstand voltage(peak) 1.2/50μs 200
3 Rated current A 1600/2500
4 Rated frequency Hz 50/60
5 Rated short circuit breaking current kA 31.5
6 Rated operation sequence O-0.3s-CO-180s-CO-180s-C
7 Rated short circuit breaking current breaking times times 20
8 Rated short circuit closing current(peak) kA 80
9 Rated peak withstand current 50
10 Rated short time withstand current 31.5
11 Fully breaking time s <0.125
12 Rated short circuit duration 4
13 Mechanical life times 10000
14 Rated operating voltage and auxiliary circuit rated voltage V 110/220
 
Mechanical characteristic parameters of circuit breaker
No. Item Unit Value
1 Contact clearance mm 18±1
2 Contact overtravel mm 6±1
3 Opening speed M/s 1.6±0.2
4 Closing speed M/s 0.8±0.2
5 Simultaneity of three phase opening and closing ms 2
6 Phase distance mm 680±2
7 Contact closing bounce time ms 3
8 Each phase conductive circuit resistance μΩ 60
9 Closing time ms 25~60
10 Opening time ms 20~50
11 Rated power frequency of energy storage motor W 110
12 Rated voltage of energy storage motor V 220
13 Max./Min. Motor voltage 120%/80%
14 Rated closing operating voltage 220
15 Max./Min. Closing operating voltage 120%/80%
16 Rated opening operating voltage 220
17 Max./Min. Opening operating voltage 120%/65%
 
Technical parameters of operating mechanism
No. Item Unit Value
1 Rated operating voltage Opening tripper V AC220
Closing tripper AC220
2 Rated resistance Opening tripper Ω 56
Closing tripper 56
3 Rated output power frequency Opening tripper W 320
Closing tripper
4 Energy storage motor power frequency W 110
5 Rated voltage of motor energy storage V AC220
6 Energy storage time s 10

 

Zw50-40.5 Outdoor Three-Phase AC High Voltage Vacuum Circuit Breaker

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
1000000 RMB
Plant Area
501~1000 square meters