YJLV22 Cable Application
yjlv22 cable is suitable for AC 50Hz power and distribution lines with rated voltage of 0.6/1kV, which can be used in fixed industrial power applications, underground tunnels, etc. Using steel wire armour offers great mechanical protection, making it rigid with a large radius.
YJLV22 Cable Standards:
IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 30kV(Um=36kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)
YJLV22 Cable CONSTRUCTION :
YJLV22 Cable Construction
Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
Insulation:Cross-linked polyethylene XLPE
Filler: Non-hygroscopic material
Binder tape: Non-hygroscopic material
Inner sheath: Polyvinyl chloride PVC
Armour: Double galvanized steel tape
Outer sheath: Polyvinyl chloride PVC
TECHNICAL DATA :
Voltage Rating Uo/U (Um) 0.6/1 (1.2)kV
Nominal Voltage DC (core-earth/core-core) :1.8/1.8kV
Test Voltage:4kV
Temperature Rating:
Flexed: 5°C to +90°C
Fixed: -35°C to +90°C
Maximum Short Circuit Temperature:
+250°C (max 5 seconds)
Minimum Bend Radius:
Single core: 15 x overall diameter
Multi core: 12 x overall diameter
Parameter
0.6/1kV-1 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable |
Nominal cross sectional area |
Insulation thickness |
Non-magnetic steel tape thickness |
Sheath thickness |
Approximate outer diameter |
Approx. |
Max.D.C resistance of conductor(20ºC) |
Current carrying capacity |
weight |
mm2 |
mm |
mm |
mm |
mm |
kg/km |
Ω/km |
In Air(A) |
In Ground(A) |
1X10 |
0.7 |
0.2 |
1.8 |
11.8 |
206 |
3.08 |
58 |
47 |
1X16 |
0.7 |
0.2 |
1.8 |
12.9 |
247 |
1.91 |
75 |
62 |
1X25 |
0.9 |
0.2 |
1.8 |
14.6 |
310 |
1.2 |
100 |
78 |
1X35 |
0.9 |
0.2 |
1.8 |
15.2 |
352 |
0.868 |
120 |
94 |
1X50 |
1 |
0.2 |
1.8 |
16.7 |
423 |
0.641 |
145 |
110 |
1X70 |
1.1 |
0.2 |
1.8 |
18.5 |
523 |
0.443 |
190 |
135 |
1X95 |
1.1 |
0.2 |
1.8 |
20.1 |
629 |
0.32 |
235 |
160 |
1X120 |
1.2 |
0.2 |
1.8 |
21.7 |
738 |
0.253 |
270 |
185 |
1X150 |
1.4 |
0.2 |
1.8 |
23.7 |
877 |
0.206 |
310 |
205 |
1X185 |
1.6 |
0.2 |
1.8 |
25.7 |
1031 |
0.164 |
355 |
235 |
1X240 |
1.7 |
0.2 |
1.8 |
28 |
1254 |
0.125 |
- |
- |
1X300 |
1.8 |
0.2 |
1.9 |
31 |
1495 |
0.1 |
- |
- |
1X400 |
2 |
0.2 |
2 |
35 |
1904 |
0.0778 |
- |
- |
|
|
|
|
|
|
|
|
|
0.6/1kV-2 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable |
Nominal cross sectional area |
Insulation thickness |
Non-magnetic steel tape thickness |
Sheath thickness |
Approximate outer diameter |
Approx. |
Max.D.C resistance of conductor(20ºC) |
Current carrying capacity |
weight |
mm2 |
mm |
mm |
mm |
mm |
kg/km |
Ω/km |
In Air(A) |
In Ground(A) |
2X2.5 |
0.7 |
0.2 |
1.8 |
13.4 |
236 |
12.1 |
- |
23 |
2X4 |
0.7 |
0.2 |
1.8 |
14.3 |
269 |
7.41 |
- |
30 |
2X6 |
0.7 |
0.2 |
1.8 |
15.3 |
307 |
4.61 |
- |
38 |
2X10 |
0.7 |
0.2 |
1.8 |
17.8 |
397 |
3.08 |
50 |
47 |
2X16 |
0.7 |
0.2 |
1.8 |
20 |
493 |
1.91 |
64 |
62 |
2X25 |
0.9 |
0.2 |
1.8 |
23.3 |
643 |
1.2 |
86 |
78 |
2X35 |
0.9 |
0.2 |
1.8 |
24.6 |
738 |
0.868 |
105 |
94 |
2X50 |
1 |
0.2 |
1.8 |
27.2 |
896 |
0.641 |
125 |
110 |
2X70 |
1.1 |
0.2 |
1.9 |
31.4 |
1164 |
0.443 |
165 |
135 |
2X95 |
1.1 |
0.2 |
2 |
35.5 |
1480 |
0.32 |
200 |
160 |
2X120 |
1.2 |
0.5 |
2.2 |
40.2 |
2164 |
0.253 |
235 |
185 |
2X150 |
1.4 |
0.5 |
2.3 |
44.2 |
2572 |
0.206 |
270 |
205 |
2X185 |
1.6 |
0.5 |
2.5 |
48.9 |
3089 |
0.164 |
310 |
235 |
|
|
|
|
|
|
|
|
|
0.6/1kV-3 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable |
Nominal cross sectional area |
Insulation thickness |
Non-magnetic steel tape thickness |
Sheath thickness |
Approximate outer diameter |
Approx. |
Max.D.C resistance of conductor(20ºC) |
Current carrying capacity |
weight |
mm2 |
mm |
mm |
mm |
mm |
kg/km |
Ω/km |
In Air(A) |
In Ground(A) |
3X2.5 |
0.7 |
0.2 |
1.8 |
13.9 |
257 |
12.1 |
- |
23 |
3X4 |
0.7 |
0.2 |
1.8 |
14.8 |
296 |
7.41 |
- |
30 |
3X6 |
0.7 |
0.2 |
1.8 |
16 |
342 |
4.61 |
- |
38 |
3X10 |
0.7 |
0.2 |
1.8 |
18.6 |
447 |
3.08 |
50 |
47 |
3X16 |
0.9 |
0.2 |
1.8 |
21 |
563 |
1.91 |
64 |
62 |
3X25 |
0.9 |
0.2 |
1.8 |
24.6 |
744 |
1.2 |
86 |
78 |
3X35 |
0.9 |
0.2 |
1.8 |
26 |
869 |
0.868 |
105 |
94 |
3X50 |
1 |
0.2 |
1.9 |
28.9 |
1074 |
0.641 |
125 |
110 |
3X70 |
1.1 |
0.2 |
2 |
33.9 |
1443 |
0.443 |
165 |
135 |
3X95 |
1.1 |
0.5 |
2.2 |
39 |
2183 |
0.32 |
200 |
160 |
3X120 |
1.2 |
0.5 |
2.3 |
42.7 |
2593 |
0.253 |
235 |
185 |
3X150 |
1.4 |
0.5 |
2.4 |
47.5 |
3155 |
0.206 |
270 |
205 |
3X185 |
1.6 |
0.5 |
2.6 |
52.1 |
3743 |
0.164 |
310 |
235 |
3X240 |
1.7 |
0.5 |
2.8 |
58.3 |
4641 |
0.125 |
365 |
260 |
3X300 |
1.8 |
0.5 |
2.9 |
63.6 |
5508 |
0.1 |
420 |
290 |
|
|
|
|
|
|
|
|
|
0.6/1kV-4 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable |
Nominal cross sectional area |
Insulation thickness |
Non-magnetic steel tape thickness |
Sheath thickness |
Approximate outer diameter |
Approx. |
Max.D.C resistance of conductor(20ºC) |
Current carrying capacity |
weight |
mm2 |
mm |
mm |
mm |
mm |
kg/km |
Ω/km |
In Air(A) |
In Ground(A) |
4X2.5 |
0.7 |
0.2 |
1.8 |
14.7 |
288 |
12.1 |
- |
23 |
4X4 |
0.7 |
0.2 |
1.8 |
15.8 |
334 |
7.41 |
- |
30 |
4X6 |
0.7 |
0.2 |
1.8 |
17 |
384 |
4.61 |
- |
38 |
4X10 |
0.7 |
0.2 |
1.8 |
20 |
509 |
3.08 |
50 |
47 |
4X16 |
0.9 |
0.2 |
1.8 |
22.7 |
649 |
1.91 |
64 |
62 |
4X25 |
0.9 |
0.2 |
1.8 |
26.7 |
880 |
1.2 |
86 |
78 |
4X35 |
0.9 |
0.2 |
1.8 |
28.3 |
1040 |
0.868 |
105 |
94 |
4X50 |
1 |
0.2 |
2.1 |
32 |
1365 |
0.641 |
125 |
110 |
4X70 |
1.1 |
0.5 |
2.1 |
38.5 |
2138 |
0.443 |
165 |
135 |
4X95 |
1.1 |
0.5 |
2.3 |
42.9 |
2638 |
0.32 |
200 |
160 |
4X120 |
1.2 |
0.5 |
2.4 |
47.4 |
3202 |
0.253 |
235 |
185 |
4X150 |
1.4 |
0.5 |
2.6 |
52.3 |
3847 |
0.206 |
270 |
205 |
4X185 |
1.6 |
0.5 |
2.7 |
57.5 |
4585 |
0.164 |
310 |
235 |
4X240 |
1.7 |
0.5 |
3 |
64.3 |
5709 |
0.125 |
365 |
260 |
4X300 |
1.8 |
0.5 |
3.1 |
70.3 |
6805 |
0.1 |
420 |
290 |