• Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
  • Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
  • Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
  • Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
  • Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
  • Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable

Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable

Type: Insulated
Conductor Type: Stranded
Application: Installation
Conductor Material: Copper
Sheath Material: Silicone
Insulation Material: Silicone
Samples:
US$ 10/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
SIHF+C / SIHF-SI+C
Material Shape
Round Wire
Range of Application
Electrical Facilities
Certification
ISO9001, CE, UL, RoHS
Brand
Aein
Transport Package
Optional
Specification
Multicore
Trademark
AEIN
Origin
Shanghai
HS Code
8544492100

Product Description

 
Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSIHF+C / SIHF-SI+C Heat and Coldness Resistant Power and Connect Cable
 
Item SIHF+C / SIHF-SI+C Heat and Coldness Resistant Power and Connect Cable
Conductor copper strand tinned
Insulation Silicone
Inner sheath  SIHF-SI+C: silicone
Shield  Copper braid tinned; coverage appr. 85%
Outer Sheath Silicone
Nominal Voltage Uo/U: 300/500 V
Operat. temp. fixed min/max  -60 °C / +180 °C; short-time: +200 °C
Temp. at conductor +180 °C
Temperature Range Fixed: -20°C to +90°C
Flexed: -5°C to +50°C
Halogen free Halogen-free acc. to IEC 60754-1
Color Optional
Certification CE
Special Features • Largely resistant to acids, bases and specified types of oil
• No flame conduction in case of fire, insulation integrity and low smoke density
• Resistant to ozone and humidty, weather-proofed
• Recommended for EMC-applications
• Rbove +100 °C and with exclusion of air, the mechanical properties of silicone cables will be reduced early, adequate ventilation should be ensured
Application Heat and coldness resistant power, control and connecting cable in electrical facilities, for lossless data and signal transmission, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no laying underground.


Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable
Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable

Sihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect CableSihf+C / Sihf-Si+C Heat and Coldness Resistant Power and Connect Cable

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now