GF302D 120A 600V Portable three phase energy meter test board with 0.04% accuracy Internal 3 Phase Standard
The GF302D portable three phase energy meter test board consists of an integrated three phase 120A current source and 600V voltage source and a class 0.04 three phase electronic reference standard meter.
The energy meter test board is particularly designed for analysis of complete metering installations and local mains conditions. The meter test bench offers high functionality combined with an excellent menu guided operation via built-in thirty keys and colored 7" touch LCD-display.
GF302D is completely programmable with features such as imbalanced loads which can be programmed to modify the voltage and current on each phase, repetitive testing where you can test the same meter an unlimited number of times. The user can change any variable such as voltage, current, Ke, frequency number of revolutions, etc all with their finger.
GF302D meter test board uses a specially designed Sentry GF12 Optical port for testing meters through the optical port. The Sentry GF12 can also be used for programing and resetting the meter by toggling to the manufacturers software. Both testing and programming/resetting can be accomplished without changing probes.
FEATURES
- Min current output 1mA
- Predefined multiple load points
- Reference meter and power source integration
- User friendly menu guided operation
- Easy verification and analysis of meter installations
- Automatic operation without need of an external PC
- Generation of harmonics in current and voltage up to the 51th
- Verification of the load conditions on metering installation
- Verification of the energy registration
- Automatic testing mechanical meter and electronic meter error
- Voltage, current, frequency, phase angle, power factor, harmonics can be regulated
- 1P2W, 1P3W, 3P3W, 3P4W can be set
- 4 quadrant measurement
- Vector diagram display and phase sequence indication on integrated colored screen
- Especially configured USB stick for storage of customer data and measurement results
PARAMETERS
Electrical parameters |
Accuracy |
0.04% |
Power Supply |
Single phase AC 85-265V, frequency 50/60Hz. |
AC Voltage Output |
Range(U1,U2,U3) |
69.3V, 120V, 240V, 480V( optional); max 400V |
Adjustment range |
(0-120)%RG(1) |
Adjustment fineness |
0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability |
0.01%/120s |
Distortion |
0.2% (Non-capacitive load) |
Output load |
each phase 25VA |
Accuracy |
0.05%RG or 0.02%RG |
AC Current Output |
Range(I1,I2,I3) |
200mA, 1A, 5A, 20A, 100A; max 125A |
Adjustment range |
(0-120)%RG |
Adjustment fineness |
0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability |
<0.01%/120s |
Distortion |
≤0.2% (Non-capacitive load) |
Output load |
100VA |
Accuracy |
0.04%RG |
Power Output |
Active power output stability |
<0.01%RG/120s |
Reactive power output stability |
<0.02%RG/120s |
Active power measuring accuracy |
0.04%RG |
Reactive power measuring accuracy |
0.1%RG |
Phase Output |
Output adjustment range |
0°-359.999° |
Output adjustment fineness |
10, 1, 0.1, 0.01 as optional. |
Resolution |
0.01° |
Accuracy |
0.02° |
Power Factor |
Adjustment range |
-1 ~ 0 ~ 1 |
Resolution |
0.0001 |
Measurement accuracy |
0.0005 |
Frequency Output |
Adjustment range |
40Hz-70Hz |
Output adjustment fineness |
5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
Resolution |
0.001Hz |
Accuracy |
0.002Hz |
Voltage /Current/Harmonic Setting Output |
Harmonic number |
2-51times |
Harmonic content |
0-40% |
Harmonic phase |
0-359.99 |
Harmonic setting accuracy |
(10%±0.1%)RD(2) |
Power Energy Measurement Error |
Active power energy |
0.04%RG |
Reactive power energy |
0.1%RG |
Power Pulse Output |
Power pulse type |
active pulse, reactive pulse |
Active power pulse output |
5V, 10mA |
Power Pulse Input |
Energy pulse type |
support active and reactive pulse, the highest frequency power pulse input is 180K. |
Communication Port |
Communication Port |
RS232, USB2.0 |
Safety |
Isolation protection |
IEC 61010-1:2001 |
Measurement Category |
300 V CAT III, 600 V CAT II |
Degree of protection |
IP20 |
Declaration of conformity |
CE certified |
Mechanical parameters |
Dimensions (W×D×H) (mm) |
445x460x158 |
Weight (kg) |
27 |
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
PHOTOS