Breaking Capacity: | 35ka, 36ka, 40ka, 50ka, 65ka, 80ka |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Open Frame |
Structure: | ACB |
Customization: |
---|
Suppliers with verified business licenses
JN22-36 Indoor earthing switch is applicable for three-phase AC power system of rated voltage up to 7.2KV~40.5KV and frequency 50/60 Hz, it widely used in many fields such as power plant, transformer substation, petrol chemical industry, metallurgy, manufacturing industry, airport, residential area, etc, for mounted at in frequency operation service indoor air insulating switchgear like tyoe KYN28 or KYN96, ABB type ZS series, etc. The application of it and its expending products can fully meet the requirement of GB, DL, IEC, DIN, VDE ad well as standards of other advanced industrial countries.
Item |
Unit |
Data |
||||
12kV |
24kV |
36kV |
||||
Rated Current |
A |
630 |
630 |
630 |
||
Rated Voltage |
kV |
12 |
24 |
26 |
||
Rated Insulation Level |
1 min Power Frequency Withstand Voltage |
Dry |
42/49 |
50/65 |
70/90 |
|
Wet |
34 |
55 |
65 |
|||
Lightning Impulse Withstand Voltage (Peak) |
75/85 |
125/145 |
150/175 |
|||
Rated Frequency |
Hz |
50/60 |
50/60 |
50/60 |
||
Rated Short-circuit Closing Current (Peak) |
kA |
50 |
63 |
63 |
||
Rated Short-time Withstand Voltage (4s) |
20 |
25 |
25 |
|||
Rated Peak Withstand Current |
50 |
63 |
63 |
|||
Rated Operating Voltage (Controller) |
V |
AC220 |
AC220 |
AC220 |
||
Auxiliary Circuit Rated Voltage |
DC24 |
DC24 |
DC24 |
|||
Mechanical Life |
times |
3000 |
5000 |
5000 |
||
SF6 Rated Air Pressure (20°C) |
MPa |
≤0.71 |
≤0.71 |
≤0.71 |
||
SF6 Rated Annual Leak Rate |
% |
≤0.5 |
||||
Operation Mode |
|
Spring Operation (Manual/Electric) |
Suppliers with verified business licenses