36mm 200A split core current transformer CE UL for Energy management
The ECS36-S series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These CTs can be mounted without removing existing cables for easier installation
Customized current ratio available.
Rated Primary Current(Amp.) 50/60Hz |
200nom(1~300A max) |
Turn ratio |
Np:Ns=1:40 |
Current Ratio |
200A/5A |
D.C. Resistance at 20 ºC |
55(mΩ)±10% |
Accuracy@ Rb=2.5VA |
0.5% |
Phase Error at Rated Current Range |
≤2' |
Operating Temperature Range |
-40~70ºC |
Storage Temperature Range |
-45~80ºC |
Dielectric Withstanding Voltage(Hi-pot) |
2.5KV/1mA/1min |
Impluse Withstand Voltage |
5KV Peak |
Insulation Resistance |
DC500V/100MΩ min |
Suppliers with verified business licenses