• 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
  • 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
  • 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
  • 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
  • 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
  • 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation

15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation

Installation Type: Pole Mounted /Substation Mounted
Comunication Port: RS232, RS485, RJ45, WiFi, Blueteeth, GPRS
Protocol: IEC61850, IEC104.IEC101, DNP3.0, Modbus
Standard: IEC/IEEE/ANSI/GB
Transport Package: Wooden/Carton
Specification: 15KV/27KV/38KV, 50HZ/60HZ, 630A/1250A
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
CHZ4
Trademark
HEMG
Origin
China
Production Capacity
5000PCS/Year

Product Description

1.0 Instruction
The CHZ4(T)-12(15/27/38) KV/630A-1250A Providing the features of a traditional re-closer, plus the bene of up to date design optimized for automation, remote control and monitoring, now or in the future.by customer demand for improved return on capital investment in the distribution network to achieve optimum performance and reliability, making use of the latest available technology in insulation, vacuum interruption and microelectronics. 
Three phase pole-top automatic circuit re-closer are designed and produced by the three kind of international advanced technology, as epoxy solid encapsulated technology, permanent magnetic actuating device, and intelligence control technology and so on.
The product is composite with solid dielectric insulted pole, permanent magnetic actuating device or motor actuating device, control unit, current transformer and vacuum interrupter and voltage sensor. Except the control unit is a single device, the others are combined together, compact frame, flexible design, easy to operate. 
The CHZ4(T)-12(15/27/38) KV/630A-1250A three phase pole-top automatic circuit re-closer is for 12kV(15KV/27KV/38KV),50/60Hz distribution system, has not only circuit breaker control and protection features, but also can automatically detect the lines running statement.
Once the load side line or equipment occur a fault, meet or exceed current setting the minimum starting current, it will be good at a per-determined action sequence, to identify the fault is transient or permanent, and auto-complete one to three re-closing.
2.0 Designing Standard
2.0.1 ANSI-IEEE-Std-C37.60-2003,
2.0.2 BS EN 60529-1992+A2:2013
2.0.3 IEEE Std.C37.60-2013, IEEE Std C57.12.29-2014
2.0.4 JB7570-1994, and DL/T813-2002
2.0.5 IEC56, IEC694, IEC62271-111

3.Specification for Vacuum Circuit Breaker                         
3.1 Ratings for ZW32-12(15) KV Vacuum Circuit Breaker
No. Item Unit Data for ZW32-12KV Data for ZW32-15KV
1 Rated Voltage KV 12 15
2 Rated insulation level
(phase to ground, phase to phase)
1 min Frequency withstand voltage Dry KV 42 50
Wet 34 45
Lighting Impulse Withstand Voltage(Peak) KV 75 110
3 Medium Interruption: Vacuum
4 Medium isolation: Solid polymer
5 Mechanism of operation (closing and shot): Magnetic
6 Assembly: Suitable weather for substation
7 Environmental operating temperature: FROM -40ºC-+50ºC
8 Position indicator: Green-closed; Open-red
9 Minimum distance of contouring of the insulation MM 400 600
10 Rated Frequency Hz 50/60
11 Rated Current A 630/800/1250
12 Rated Min Start-up Current Numerical A adjustable
Permissible deviation % ±10
13 Rated Fault Interrupter Capacity KA/3s 12.5/20
14 Rated Fault Symmetrical Making Current KA 12.5/20
15 Rated Short-Time Withstand Current KA 12.5/20
16 Rated Peak Withstand Current KA 12.5/20
17 Interrupting Time(Max) (Cycle) s No more than 4
18 The conditions of different phase earthed fault short-circuit breaking current KA 17.3
19 Rated Cable Charging Breaking current A 25
20 Rated Operating Sequence   O-0.1s-CO-2s-CO-2s-CO-C
21 Rated Operation Voltage V AC/DC110/125/220/240
22 Rated Short-Circuit Current Breaking Times Time  
90%~100% Rated Short-Circuit Current volume 16
45%~55% Rated Short-Circuit Current volume 44
15%~20% Rated Short-Circuit Current volume 56
23 Mechanical Life (Mechanical stability) Time/Unit Operation 15000
24 Current Transformer Primary Rated Current A 600/1000
Secondary Rated Current 1 or 5
Accuracy Grade CL 0.2/5P20
Capability VA 15
25 Special Manual Closing Mechanism  
 
optional
26 Earthing   Solidly Earthed
                   
 
 3.2 Ratings for ZW32-27(38) KV Vacuum Circuit Breaker
 
No.
Item Unit Data for ZW32-27KV Data for ZW32-38KV
1 Rated Voltage KV 27 38
2 Rated insulation level (phase to ground, phase to phase) 1 min Frequency withstand voltage Dry KV 65 95
Wet 50 80
Lighting Impulse Withstand Voltage(Peak) KV 145/150 185
3 Medium Interruption: Vacuum
4 Medium isolation: Solid polymer
5 Mechanism of operation (closing and shot): Magnetic
6 Assembly: Suitable outdoor for substation or pole mounted
7 Environmental operating temperature: FROM -40ºC-+50ºC
8 Position indicator: Green-closed; Open-red
9 Minimum distance of contouring of the insulation MM 680 900
10 Rated Frequency Hz 50/60
11 Rated Current A 200A/400A/630A/1250A
12 Rated Min Start-up Current Numerical A Adjustable
Permissible deviation % ±10
13 Rated Fault Interrupting Capacity KA/3S 12.5/20
14 Rated Symmetrical Making Current KA 12.5/20
15 Rated Short-Time Withstand Current KA 12.5/20
16 Rated Peak Withstand Current KA 12.5/20
17 Interrupting time(Max)(Cycle) S Not more than 4
 18 The conditions of different phase earthed fault short-circuit breaking current KA 12.5 20
19 Rated Cable Charging Breaking current A 25
20 Rated Operating Sequence   O-0.1s-CO-2s-CO-5s-CO-C
21 Rated Operation Voltage V AC/DC110/125/220/240
22 Rated Short-Circuit Current Breaking Times Time  
  90%~100% Rated Short-Circuit Current volume   16
  45%~55% Rated Short-Circuit Current volume   44
  15%~20% Rated Short-Circuit Current volume   56
23 Mechanical Life (Mechanical stability) Time/unit Operation 10000
24 Current Transformer Primary Rated Current A 600/1000
    Secondary Rated Current   1 or 5
    Accuracy Grade CL 0.25/5P20
    Capability VA 15
25 Special Manual Closing Mechanism   Option
26 Farthing   Solidly Earthed
                   
 
4.Intelligent Controller Communications Cubicle
The product is supplied complete with an CHK4(T/S) series controller to achieve the various functions Including of measurement, protection, control and communication requirements. The controller can achieve the functions are as follows:
CHK4 CONTROLS FUNCTIONS AND CHARACTERISTICS
1. Control panel is operated by manual or PC
2. Remote control is by through SCADA
3. Total time maximum opening 3 cycles/50ms for 60hz
4. Re-close time and programming step Programmable
5. Independent calibration groups, minimum
Automatic Protection Group Selection is used to change the protection, group depending on the direction of power flow. This allows the re-closer to be correctly graded with devices downstream regardless of the power flow direction.
3/4
each of which can be configured
with completely separate protection characteristics with different inverse time curves and setting currents. The number of protection groups available to the operator can be configured, thereby restricting or enabling access to protection settings as required
6 Operation with dead line With battery bank if AC power is lost 1.Back up battery bank power for 48hours without charging
2.100times operation within 48hours
3.Battery bank is charged by intelligent charger in controller cabinet from outside PT
7. It is with Control and microprocessor protection
8. Selection of number of operations fast 0-4 from IEC curve
9. Selection of number of slow operations 0-4 from IEC curve
10. Selection of number of lock operations 1-4 IEC curve
11. Buttons with indicators (LED's). Applicable control with microprocessor relay
12. Modification of curves by time (dial) tap in current and adding time-definite FOR IEC 5 Curve and IEEE 3 curve
13. Minimum programmable LED's. It applies to control with microprocessor relay. 4 (u)
14. Automatic Re-closer locking
15. Remote operation lock
16. Levels of access codes to configuration
17. Fault recorder
18. FOR PROTECTION CURRENT TRANSFORMERS:
18.1 Relation For Phases 1000/600/400/200/100:1/5
18.1.1 Precision for protection: +/- 5%
18.1.2 Material of the bushings Polymer
18.2 Relation for Ground 200/100/50:1/5(POTION)
18.2.1 Precision for protection 5P
18.2.2 Material of the bushing Polymer
19. FEATURES OF THE ELECTRONIC CONTROL
19.1 Type of installation: Outdoor for mounting substation or pole
19.2 Degree of protection: IP65/IP54
19.3 Access Front
19.4 Memory type: Non-volatile
20. THE CONTROL UNIT SHOULD INCLUDE:
20.1 Liquid crystal display LCD(3"x1"/77mmx27mm)
20.2 Membrane keyboard
20.3 LED's for indication of the State of the control, Re-closer (open/close) and the shooting conditions
21. OPERATION BUTTONS TO ENABLE / DISABLE THE FOLLOWING FUNCTIONS:
21.1 Ground-fault trip
21.2 Automatic Re-closer
21.3 Remote control
21.4 Buttons for closure and manual (local) tripping of the unit
21.5 Function of hot line tag to configurable buttons for change of setting and activation of control logic or blocking local group.
22 PROTECTION FUNCTIONS
22.1 Instantaneous over current for phase, neutral and negative sequence 50 relays PGQ/50N
22.2 Timed over current for phase, neutral and negative sequence 51 relays PGQ/51N
22.3 Sequence Components
Negative, positive and zero phase sequence currents and voltages can be
monitored and logged.
In addition, the negative phase sequence current protection can be used for
detection of low-level phase-to-phase faults in the presence of high level three phase
loads. Inverse Time, Definite Time and Instantaneous operation is available.
Setting current range: 10 - 1260 A
22.4 Sequence Coordination Sequence Coordination allows a recloser to coordinate it's trip sequence with
another recloser downstream
22.5 Auto-re-closer Relay 79 (sequence 1,2,3,4)
Operating Sequence
Reclose times are individually selectable. The operating sequence is defined by:
O - 1st rt - CO - 2nd rt - CO - 3rd rt - CO
where rt = reclose time.
where O = open.
where C = close.
1st Reclose Time range: 0.2 - 180 sec
2nd Reclose Time range: 2.0 - 180 sec
3rd Reclose Time range: 2.0 - 180 sec
Timing resolution: 0.1 sec
Recovery/ Reset Time: 0.1 - 180 sec
Sequence Reset Timing resolution: 1 sec
22.6 Trips to Lockout Overcurrent and fault trips to lockout are selectable between 1 and 4. A separate
setting is available for Sensitive Earth Fault and Negative Phase Sequence.
22.7 Loss of phase
Loss of phase protection trips the re-closer if phase-earth voltage on one or two, phases falls below a set voltage threshold for a set length of time.
Threshold voltage range: 2 - 15kV
Voltage resolution: 1V
Time range: 0.1 - 100 sec
Time resolution: 0.1 sec
22.8 Live load blocking
Live load blocking prevents a re-closer from closing if any of the load side terminals
are live.
Live Load Threshold Voltage range: 2 - 15kV
22.9 Dead lockout
 
Dead lockout prevents a reclose unless one or more of the source side or load side
terminals are live. If all terminals are dead, then the controller goes to lockout
22.10 Envelope and low frequency
This feature trips the re-closer when the system frequency exceeds the under and
over frequency trip threshold values. Frequency tripping range: 45 - 65 Hz
Relay 81
Frequency calculation: Once per cycle over a two-cycle period
Number of under/over frequency cycles before tripping: 2 - 1000
Accuracy: ±0.05Hz
22.11 Over voltage Relay 59
22.12 Low voltage Relay 27
22.13 Distance Relay 21
22.14 Directional blocking
Directional protection
 
67 relay PGQ/67N
a protection feature that restricts tripping on faults to a
designated side of the re-closer. It prevents nuisance tripping if network
conditions are causing "false" earth faults. In radial systems, Directional Blocking
prevents nuisance tripping by blocking faults in the source direction and only responding to faults in the load direction.
Distinct protection for faults in the forward and reverse direction. A forward fault may
use a different time-current curve and settings to a reverse fault (i.e. these are
individually selectable). Both the forward protection and reverse protection are
operating at the same time. This is an additional protection feature
22.15 Cold load picks up(OPTIONAL)
Cold load pick-up allows for a loss of diversity when a load has been without supply
for a period.
Multiplier range: 1 - 5
Multiplier resolution: 0.1
Time Constant range: 1 - 480 min
Time constant resolution: 1 min
22.16 High impedance/conductor broken failure Optional
22.17 harmonic optional
22.18 Protection time-current curves: 1. IEC/IEEE ,2.ANSI(OPETIONAL)
3.(optional Non Standard Inverse Time Curves)
IEC 60255 CURVES Inverse,Very Inverse and Extremely Inverse.
IEEE C37.122 Moderately Inverse,Very Inverse and Extremely Inverse.
22.19 Instantaneous protection
Instantaneous protection works by tripping the re-closer if the line current exceeds
the Instantaneous Multiplier x Setting Current.
Multiplier range: 1 - 30
Resolution of setting: 0.1
Max effective setting: 12.5kA
22.20 Definite time protection
Definite Time is an alternative to Inverse Time protection. It works by tripping the
Re-closer at a fixed time after pick-up.
Setting current range: 10 - 1260A
Definite time resolution: 0.1 sec
Definite time range: 0.01 - 100 sec
Setting current resolution: 1A
22.21 Sensitive Earth Fault (SEF) SEF trip Current Range:          5A-25A
MIN 5A(to Ground)/MIN25A(to phases)
SEF operating time range:          0.1-999sec
SEF trip current setting resolution:          1A
SEF operating time resolution:          0.1S
22.22 Under / Over Voltage Protection
When selected, and a nominal Phase to Earth System operating voltage is set, the UOV Protection works within a defined threshold above and below the specified
voltage.
Under Voltage Lower Threshold Range:
50% - 88%
Over Voltage Upper Threshold Range: 112% - 150%
Trip After X Secs Range: 0 - 300 Seconds
Phase Logic
1.When ALL phases deviate beyond thresholds
2.When ANY phase voltage deviates beyond the thresholds
3.When the numerical AVERAGE of all phase Voltages deviates beyond the threshold.
22.23 Inrush restraint
Inrush restraint raises the phase and earth threshold currents for a short period of
time to allow for short duration inrush currents when closing onto a load.
Multiplier range: 1 - 30
Multiplier resolution: 0.1
Time range: 0.05 - 30 sec
Time resolution: 0.05 sec
23 MEASUREMENT FUNCTIONS  
23.1 Voltage By phase,line and neutral
23.2 Current (0-1250A) By phase ,line and neutral
23.3 Power (Active and reactive) By phase and line
23.4 Energy (Active and reactive) By phase and line
23.5 Power factor By phase and line
22.6 Load profile registry (Amperage, voltage, power,energy  power factor) 1.registry Every 15 minutes
2.Optional adjustable (0-60MIN)
24 ADDITIONAL  FUNCTIONS:
24.1 Events Registrar 1.216 records of events
2.216 records of remote control
3.216 records of events of failure
4.45 records for fault waveform(15before and 30 after)
5.216 records of history events
24.2 The battery status monitor
24.3 Inputs and outputs programmable by the user
24.4 Native protocol Mod-bus/DNP3.0 profile
25 COMMUNICATION PORTS:
25.1 RS232 for Setting of communication protocols and Maintain of the control by PC
25.2 RJ45 for Setting, Program and Receiving of control BY PC
25.3 RS-232 for communication With DNP 3.0 /Mod-bus interface
25.4 RS-485 for communication With DNP 3.0 /Mod-bus interface
25.5 RJ45 for remote communication With DNP 3.0/IEC61850 standard interface
25.6 GRPS or Bluetooth or WI-FI or radio to connect with laptop
25.7 Unit with 1 or 2 Fiber optic port and 3 RJ45 Ethernet communication (option)
25.8 Protocol IEC60870-5-104/IEC69870-5-101 /DNP3.0/MODBUS/IEC61850(option)
25.9 COMMUNICATION BETWEEN RELAYS(OPTIONAL)
26 Supply voltage: 110/125/220/220VAC/DC(OPTIONAL)
27 Frequency: 50Hz/60 Hz(OPTIONAL)
28 Back-up batteries: sealed free maintance ,rechargeable in control box ,monitor of power on diagnostic and continuous self monitoring 1.2AH/7AH/17AH/24AH(OPTIONAL)
2.2x12V=24VDC or 4x12v=48VDC
3.48hours with 20w if loss of power
29 Life years of recloser 10years
Life years of battery 5 years
30 Integrated battery charger/monitor is included
31 12VDC integrated auxiliary output to power a radio or moden another device for remote or local data transmission
32 Included of Heating resistors
33 Included of Control cable  15M and power cable from PT (option)
34 Included of Setting ,Programming and Receiving software
35 Including of ac lamps and heaters of moisture contol
36 Including of electricnic magnetic lock for control box
37 Microprocessor realy in the front will be with IP20 to avoid of dust ,insert ,air contaminats ,high humidity and vibration.
38 Main Protection Function Schematic
   
 
 
         

 
 
 
 
 
 
 
 
 
 
 
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation
Registered Capital
500 RMB
Plant Area
1001~2000 square meters