Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: Normal Type Circuit Breaker
Installation: Fixed
Structure: MCCB
Poles Number: 3
Customization:
Gold Member Since 2008

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
nsx
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification
CE, CCC
Color
Black
Transport Package
Standard Export Package
Specification
ce
Trademark
KASAN. OEM
Origin
Zhejiang China
Production Capacity
5000PCS/Month

Product Description


MCCB 125A Low Voltage MCCB Moulded Case Circuit Breaker MCCB Nsx
NSE,NSX,NSC,NSD moulded case circuit breaker,
NS MCCB adopt MERLIN GERIN technic
NS series moulded case circuit breaker/mccb is one of the most advanced type breakers in the world, which adopt international advanced design and manufacture fechnology. They are suitable for short circuit and overload protection for circuit of AC 690V 50/60Hz, rated current from 12.5A to 630A. It takes protect effect when mouse cage motors non-frequent start, breaking off working and protecting overload, short circuit and lacking voltage.

Tripping Characteristics of MCCB
Rated Current of Release(A) Thermodynamic Release (ambient temp +40C) Operational Current of Magnetic Release(A)
1.05In(cold state) inoperative time(h) 1.30In(heat state) operative time(h)
In≤ 63 ≥ 1 <1 10In+20%
63 ≥ 2 <2 10In +20%
100 ≥ 2 <2 5-10In+20%

Rated Current of Release(A) Thermodynamic Release (ambient temp +40C) Operational Current of
Magnetic
Release(A)
1.0In(cold state)operative time(h) 1.20In(heat state)operative time(h) 1.50In(heat state)operative time(h) 1.01In(heat state)operative time(h)
12.5≤ In≤ 400 ≥ 2 <2 ≤ 4min S 12In+20%
Rated current of release(A) Thermodynamic release(ambient temp+40 ) Operation current of magnetic release(A)
1.05ln(cold state)
inoperative time(h)
1.30ln(heat state)
inoperative time(h)
ln 63  1 1 10ln 20%
63 ln 100 2 2 10ln 20%
100 ln 630 2 2 5-10ln 20%
 
Rated current of release(A) Thermodynamic release(ambient temp+40 ) Operation current of magnetic release(A)
1.0ln(cold state)
inoperative time(h)
1.20ln(heat state)
inoperative time(h)
1.50ln(heat state)
inoperative time(h)
1.0ln(heat state)
inoperative time(h)
12.5 ln 400 2 2 4min 2S Tp 10S 12ln 20%

Specifications:
Type Rated current(A) Pole No. Rated insulating voltage (V) Rated operating voltage Arcing over distance (mm) Ultimate short circuit breaking capacity(kA) Services short circuit breaking capacity(kA) Operation performance (Endurance)
ON OFF
NS-100D 12.5, 16, 20, 25, 32, 40, 50, 63, 80, 100 3
4
950 690 0 18 18 1500 8500
NS-100N 25 25
NS-100H 70 70
NS-100L 150 150
NS-160D 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 25 25 1000 7000
NS-160N 36 36
NS-160H 70 70
NS-160L 150 150
NS-250D 160, 180, 200, 225, 250 25 25 1000 7000
NS-250N 36 36
NS-250H 70 70
NS-250L 150 150
NS-400D 200, 225, 250, 300, 315, 400 35 35 1000 4000
NS-400N 15 45
NS-400H 70 70
NS-400L 150 150
NS-630D 315, 350, 400, 500, 600, 630 35 35 1000 4000
NS-630N 45 45
NS-630H 70 70
NS-630L 150 150