• Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
  • Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
  • Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
  • Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
  • Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester
  • Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

Type: Light Duty, Heavy Duty
Application: Electric Power Distribution Substation
Certification: Kema Type Test Report
Standard: IEC60099-4
Used for: High Voltage/ Medium Voltage
Housing Material: Silicone, Polymer, Porcelain, Ceramic
Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
YH10W5-10
Delivery Time
Shipped in 15 Days After Payment
Purpose
Over-Voltage Protection
Accessory
Disconnector, Mounting Plate, NEMA Bracket
Color
Brown, Gray
Transport Package
Wooden Case
Trademark
YONGDE
Origin
Zhejiang, China (Mainland)
Production Capacity
1500 Piece/Pieces Per Day for 11kv Surge Arrester

Product Description

Kema 11kV Surge Arrester Zinc Oxide Lightning Arrester 

Lightning Arrester Characteristics:
1. The Core column applied winding structure, Polymer Housed core pillar molded on the core column, with almost no internal air gap, and outstanding sealing performance Simple in structure, small in size and light in weight.
2. Polymer Housed with silicone rubber, explosion-proof ZnO varistor as the core component is large
in flow capacity.
3. International standard IEC 60099-4 and ANSI 62.22, and with high reliability. With fully insulated tops, the product can be applied to the complete cabinet installation, which can reduce the designing size of cabinet.
4. Products with detachment device can provide signals for quitting operation when failure occurs,
avoiding arrester explosion, and it is maintenance-free.
5. Polymer housed products with a six CTI level, creepage distance meets the requirements of IV level in heavy pollution areas.

Technical Parameters:

Type YH10W5-10/27.6    
Rated voltage---------kV 10 4/10μS High current impulse kA  100
MCOV  ----------------kV 8.4 Lightning impulse withstand kV 110
Nominal Current-------kA 10 Power frequency voltage withstand(dry/wet)kV 28
Residual voltage of steep impulse----at 5kA(kV) 30 0.1S TOV--------------kV 12
8/20μS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) 27.6 1S TOV----------------kV 11.5
Residual voltage of switching impulse current kV (peak value)----at 1kA  (kV) 21.1 10S TOV---------------kV 11
1mA D.C reference voltage (kV) 14.2 1200S TOV-------------kV 10
Line discharge level 1 Creepage distance ----mm 434
2mS long duration impulse current A 400 Material employed in series non-linear resistor Zinc oxide 

Production flow:

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

 

 

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

Kema 11kv Surge Arrester Zinc Oxide Lightning Arrester

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
148
Year of Establishment
2002-11-21