Fault distance locating | ||
Distance measurement mode | Low voltage impulse Impulse current | |
Sampling frequency | 100MHz | |
Resolution Ratio | Low voltage impulse:1m Impulse current:4m | |
Voltage of low voltage impulse | 30V | |
Distance measurement range | 30km | |
Blind zone | 2m | |
Magnetic sound synchronization pin-pointing: | ||
Audio signal transmission band | Mid-frequency 400Hz ,bandwidth 200Hz. | |
Gain of signal channel | 80dB | |
Accuracy of pin-pointing | 0.1m | |
Route tracing: | ||
(M)Receiving frequency | 1kHz | |
(M)Gain | 80dB | |
Generator for route tracing: | ||
(T)Transmitting frequency | 1kHz | |
(T)Transmitting power | ≥3.5W | |
Output | Open circuit voltage≥100Vp-p Short circuit voltage ≥300mA Auto matching according the actual loading Auto short circuit protection | |
Power supply: | ||
Battery | built-in Li-ion battery pack, nominal voltage 7.4V,Capacity 3000mAH | |
Power consumption | RCI-700TM 400mA ,RCI-700TT 500mA | |
Charger | Input AC100-240V, 50/60Hz; output 8.4V, DC 1A | |
Charge time | <4 hours | |
Display | ||
Main unit 1200M | 320*240 LCD | |
Generator | Meter | |
Other | ||
Volume | 270*220*80mm M/T | |
Weight | 1.5kg M/T | |
Working condition | ||
Tem. | -10ºC-40ºC | |
Humidity | 5-90%RH | |
Elevation | <4500m | |
No | Fault | Fault form | Distance test method | Pin-pointing method |
1 | Low resistance | Megger:0 Multimeter:< 200Ω | Low voltage impulse | Audio-frequency(optional) |
Audio magnetic synchronous | ||||
2 | Open circuit | Conductor disconnection | Audio magnetic synchronous | |
3 | High resistance | Megger:>0 Or: Megger:0 Multimeter:≥ 200Ω | Impulse current | |
4 | Breakdown | Megger:insulation normal Withstand voltage test:no |