Conditions of Use: |
Land Use |
---|---|
Usage: | Common Units |
Output Type: | AC Three Phase |
Cooling Method: |
Water Cooling |
Installation Method: |
Fixed |
Generator Type: |
Diesel Generator |
Customization: |
---|
Suppliers with verified business licenses
Technical specification | |
input | |
voltage | Jumper selectable |
95-132V ac or | |
190-264V ac | |
frequency | 50-60 Hz nominal |
phase | 1 |
output | |
voltage | Max 90V dc at 207V ac input |
Current | Continuous 4 A dc |
Intermittent 6A for 10 secs | |
resistance | 15 ohms minimum |
regulation | +/- 1.0% (see note) |
Thermal drift | 0.05% per deg.c change in AVR ambient (note 2) |
Typical system response | |
AVR response | 20 ms |
Filed current to 90% | 80 ms |
Machine volts to 97% | 300ms |
External voltage adjustment | +/- 10% with 1 k ohm 1 watt trimmer(see note 3) |
Under frequency protection | |
Set point | 95% Hz(see note 4 ) |
slope | 170% down to 30 Hz |
Unit power dissipation | 10 watts maximum |
Build up voltage | 4 volts @ AVR terminals |
Environmental | |
Vibration | 20-100 Hz 50mm/sec |
100 Hz 2kHz 3.3g | |
Operating temperature | -40 to + 70c |
Relative humidity 0-70c | 95% (see note 5) |
Storage temperature | -55 to +80c |
Suppliers with verified business licenses