• HVHIPOT GDPD-3000C Portable Partial Discharge Detector

HVHIPOT GDPD-3000C Portable Partial Discharge Detector

After-sales Service: YES
Warranty: 1
Processor: High performance intelligent processor.
Screen: 4.3inch Touch Screen.
Operation keys: PVE film keyboard.
TF memory card: 4G-32G.
Customization:

360° Virtual Tour

Diamond Member Since 2011

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
GDPD-3000C
Headphones
Min. 8Ω.
External probe
Ultrasonic probe extension line 250mm.
Enclosures material
ABS+PC Plastique.
Weight
0.7kg;
Dimension
241*126*189mm
Transport Package
Wooden Case
Specification
ISO, SGS
Trademark
HV HIPOT
Origin
Wuhan, China
Production Capacity
5000PCS/Year

Product Description

General Infomation

GDPD-3000C Portable Ultrasonic Partial Discharge Detector uses advanced cloud computing and automatic modeling technology to achieve the partial discharge signal measurement, recording, transmission, storage, analysis and exchange, providing powerful technical support for on-site measurement of partial discharge. The measurement personnel collect the partial discharge information by using GDPD-3000C, and the cloud computing can be used to intelligently diagnose the insulation state of detection equipment in real time.
 

Specification

Hardware
Processor High performance intelligent processor.
Screen 4.3inch Touch Screen.
Operation keys PVE film keyboard.
 
 
Interface
1. 3.5mm stereo headphone interface
2. DC LV current charging interface
3. USB 2.0 3G wireless network interface
4. TF memory card interface
5. External probe sensor interface
TF memory card 4G-32G.
Headphones Min. 8Ω.
External probe Ultrasonic probe extension line 250mm.
Enclosures material ABS+PC Plastique.
Weight 0.7kg;
Dimension 241*126*189mm

                      
Operating Environment
Operation temperature 0~55ºC.
Operation humidity 0~90% RH, non-condensing.
IP rates 54

 
Ultrasonic Sensor Parameters
Measuring range -20dBµV~65dBµV.
Resolution 1dB.
Accuracy ±1dB.
Sensitivity -65dB.
Frequency 20KHz-100kHz.
Diameter 16mm.
Test source 25dB~35dB.

 
TEV Parameters
Sensor Capacitive.
Measuring range 0dBµV~60dBµV.
Resolution 1dB.
Accuracy ±1dB.
Max Number of Pulses/Cycle 655.
Min number of pulses 5Hz

 
Power Supply
Internal battery 3.7V, 5.6Ah rechargeable Lithium-ion.
Typical operating time Approx. 6 hours.
Battery protection Auto shutdown time, default 10 mins.
Rated voltage of charger 90-264V AC.
Charging voltage/current 5V/2.4A.
Charging Time Approx. 9 hours.


HVHIPOT GDPD-3000C Portable Partial Discharge Detector
HVHIPOT GDPD-3000C Portable Partial Discharge Detector
HVHIPOT GDPD-3000C Portable Partial Discharge Detector
HVHIPOT GDPD-3000C Portable Partial Discharge Detector
HVHIPOT GDPD-3000C Portable Partial Discharge Detector

HVHIPOT GDPD-3000C Portable Partial Discharge Detector

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now