72.5kv/145kv 40ka Double Circuit Breakers Pass/Hgis
72.5kv/145kv 40ka Double Circuit Breakers Pass/Hgis
72.5kv/145kv 40ka Double Circuit Breakers Pass/Hgis
72.5kv/145kv 40ka Double Circuit Breakers Pass/Hgis

 
Bitmap
TECHANICAL SPECIFICAITON DATA SHEET 
        M00  72.5KV/145KV PASS PLUG AND SWITCH SYSEM
ITEM  DESCRIPTION UNIT 72.5KV 145KV
1 GENERAL SERVICE CONDITIONS
1.01 Installation type   Indoor/Outdoor Indoor/Outdoor
1.02 Altitude above sea level    ≤1000M ,Adjuatable to 5000m ≤1000M,adjustable to 5000m
1.03 Standard   IEC 62271 IEC62271
1.04 Extinction medium   SF6 SF6
1.05 Maximum ambient air  temperature °C (+40ºC) (+40ºC)
1.06 Minimum ambient air temperature  °C (-30ºC) (-30ºC)
1.07 Relative humidity % ≤100%  day average  ,≤95% month average ≤100%  day average  ,≤95% month average
1.08 Wind pressure (wind speed not more than 34m/s) Pa 700 700
1.09 Solar radiation according to IEC 894 W/m2 <1000 <1000
1.10 Seismic acceleration according to IEC 1166 g >0.5 horizontal,>0.25 vertical  >0.5 horizontal,>0.25 vertical
1.11 Degree of protection according to IEC 60529 IP class 44 44
1.12 Pollution level according to IEC 60815   IV IV
1.13 Anti-corrosion of tank   Yes Yes
1.14 Ice Thickness mm 10 10
2 Weight of Equipment
2.01 SBB Module Kg 2330 2620
2.02 SBB Support frame  Kg 150 150
2.03 SBB Conntrol Panel Kg 80 80
2.04 SBB SF6 Gas Kg 40 50
2.05 Total weight of SBB PASS Kg 2600 2900
3 Surface Finishing 
3.01 Support structure(Hot-dip galvanised  according to DIN50976) um 85 85
3.02 Surface painting    NO NO
4 Electrical Data 
4.01 Number of poles   2 2
4.02 Number of phases   3 3
4.03 Type of execution   Outdoor Outdoor
4.04 Assigned frequency (fr) Hz 50/60 50/60
4.05 Voltage Characteristics      
  Nominal voltage of the system kV 66 132
  Maximum equipment voltage kV 72.5 145
4.06 Level of insulation      
  Rated voltage supported at industrial frequency (Ud)(1min) kV    
  To ground kV 140 275
  Across the isolating distance  kV 160 315
  Assigned voltage supported to the lightning impulse (peak)      
  to ground kV 325 650
  across the isolating distance  kV 375 750
5 Bushing 
5.01 BIL exterior of Bushing kV 375 750
5.02 Interior BIL of Bushing kV 325 650
5.03 Bushing Materual   Porcelain/Composite Porcelain/Composite
5.04 Rated voltage kV 72.5 145
5.05 Rated Current  A 3150 3150
5.06 Rated power frequency withstadn voltage  kV 140 275
5.07 Rated light impulse withstand voltage kV 325 650
5.08 Maximum dynamic current kAp 100 100
5.09 Duration of the short-circuit assigned (tk) s 4 4
5.10 Patial discharge level 46kV pC at 46kv ≤5 at 58kv≤5
5.11 Radi inerference Voltage level Uv ≤2500 ≤2500
5.12 Power frequency withstand voltage (15min) at 100Kpa /20ºC   46 58
5.13 Arcing distance mm 800 1452
5.14 Creepage distance mm 2250 4500
5.15 Forces that act on the concrete bases during the operation      
5.16 a) Vertical N 1250 1250
5.17 b) Horizontal N 750 750
5.18 c) transversal N 1000 1000
6 DIMENSIONS      
6.01 A) hIGH mm 3700 4500
6.02 b) Wide mm 2400 4100
6.03 c) Length mm 2700 2700
7 CIRCUIT BREAKER
7.01 Standard      IEC 52271-100 IEC 52271-100
7.02 Type   three-phase three-phase
7.03 Extinction medium Gas SF6 SF6
7.04 Number of poles   3 3
7.05 Number of cameras per pole   1 1
7.06 Type of installation   Outdoor Hybrid bay Outdoor Hybrid bay
7.07 Assigned frequency (fr) Hz 50/60 50/60
7.08 Tension characteristics      
7.09 System Voltage kV 66 132
7.10 Nominal voltage of the equipment kV 72.5 145
7.11 Rated voltage supported at industrial frequency (Ud) phase-phase, phase-earth and through open switch kV 140 315
7.12 Assigned voltage supported to the impulse type ray (Up) phase-ground, between phases and through open switch   325 650
7.13 BIL interior (inner) kV 325 650
7.14 Current characteristics      
7.15 Rated current in continuous service (Ir) A 3150 3150
7.16 Rated short-circuit current (Ics) kA 40 40
7.17 Short circuit current assigned (Ip) kAp 100 100
7.18 First pole factor   1.5 1.5
7.19 Rated short-circuit duration (tk) s 3 3
7.20 Assigned sequence of maneuvers O-0, 3s-CO-3min-CO   yes yes
7.21 Number of mechanical operations TIMES 6000 6000
7.22 Pole discrepancy logic   yes yes
7.23 Anti-pumping device   yes yes
7.24 CHARACTERISIC FOR TERMINAL FAULT (ACCORD TO IEC62271-100)
7.25 Short circuit breaking current  KA 40 40
7.26 Short circuit making  current  KA 100 100
7.27 Recovery voltage KV 63 86
7.28 TRV Peak value  KV 124 171
7.29 Rate of rise of recovery voltage (RRRV) KV/US 1.47 2
7.30 OPENING TIME (AT RATED VOLTAGE)   32 32
7.31 CLOSING TIME(AT RATED VOLTAGE)   85 85
7.32 MINIMUM ARCING TIME MS 7 7
7.33 MINIMUM CLEARING ARCING TIME MS 50 50
7.34 MAXIMUM BREAK TIME   60 60
7.35 PEAK CURRENT VALUE RATED TO PEAK VALUE FOR SYMMETRICAL SHORT CIRCUIT CURRENT  PU 1.21 1.21
7.36 DURATION OF MAJOR LOOP MS 11.5 11.5
7.37 CHARACTERISTIC FOR SHORT LINE FUALT (L90 DUTY CYCLS TO IEC62271-100)
7.38 Short line fault current    36 36
7.39 TIME DELAY    2 2
7.40 TRV SIURCE CHARACTERISTICS      
7.41 TRV PEAK VALUE Uc   144 144
7.42 Time to reach peak t3      
7.43 Rated of rise of recovery voltage (RRRV)   2 2
7.44 CHARACTERITIC FOR OUR OF PHASE MAKING AND BREAKING ACCORDING TO IEC62271-100
7.45 Out of phase breaking current    10 10
7.46 out of phase voltage factor    2.5 2.5
7.47 CHARACTERISTIC FOR CAPACITIVE CURRENT SWITCHING (LC1 LC2 ACCORDING TO 62271-100)
7.48 RATED LINE CHARGING BREAKING CURRENT  A 50 50
7.49 RATED CABLE CHARGING BREAKING CURRENT  A 160 160
7.50 VOLTAGE FACTOR K PU 2 2
7.51 Auxiliary voltage for heating and lighting V 220 220
7.52 Number of reserve auxiliary contacts      
7.53 a) Opening   10 10
7.54 b) Closing   10 10
7.55 Closing and opening devices      
7.56 a) Supply DC voltage assigned (Ua) Vcc 110 110
7.57 b) Number of opening coils per mechanism   2 2
7.58 c) Number of closing coils per mechanism   1 1
7.59 d) Consumption of the closing coil W 253 253
7.60 e) Consumption of the opening coil W 297 297
7.61 f) Opening coil voltage range % 60-120 60-120
7.62 g) Voltage margin of closing coil % 85-110 85-110
7.63 Operation counter by mechanism   yes yes
7.64 Data of the operation mechanism      
7.65 a) Type   SPRING SPRING
7.66 b) Consumption for closing W 3000 3000
7.67 c) Consumption for opening W 1700 1700
7.68 d) Voltage margin for normal operation of the mechanism V 26.4 26.4
7.69 e) Degree of protection in accordance with IEC 60947 - 1   yes yes
7.70 f) REMOTE-DISCONNECTED-LOCAL switch   yes yes
7.71 Alarms and indicators      
7.72 a) Low gas pressure (two states)   yes yes
7.73 b) Fault in the control device   yes yes
7.74 c) Pole discordance   yes yes
7.75 d) Position local / remote status control box   yes yes
7.76 e) Spring distension   yes yes
7.77 f) Terminal monitoring trip coils   yes yes
7.78 Mechanism engine data      
7.79 a) Type   Electric Electric
7.80 b) Tension Vcc 110 110
7.81 c) Power W 400 400
7.82 d) Operation counter yes / no   yes  yes 
7.83 e) Excessive operation indication yes / no   no no
7.84 f) Operating voltage margin % 10 10
7.85 Nominal motor current A 3,5 +/- 1,5 3,5 +/- 1,5
7.86 Inrush current A 10 +/- 1,5 10 +/- 1,5
8 DISCONNECTOR      
8.01 Model   yes yes
8.02 Standarda   IEC 62271-102 IEC 62271-102
8.03 Type of installation   Outdoor Outdoor
8.04 Type of operation   three phase three phase
8.05 Number of combined switches   1 1
8.06 Type of connection disconnector construction   Compressed air Compressed air
8.07 Assigned frequency (fr) Hz 50/60 50/60
8.08 Tension characteristics   Single pressure Single pressure
8.09 System Voltage kV 66 132
8.10 Rated voltage of the equipment kV 72.5 145
8.11 Assigned voltage supported to the lightning impulse (Up), inside the Hybrid Bay      
8.12 a) On land and between poles kV 325 650
8.13 b)      A través de la distancia de seccionamiento kV 375 750
8.14 Rated voltage supported at the industrial frequency (Ud) kV 72.5 145
8.15 a) On land and between poles kV 140 275
8.16 b) Through the sectioning distance kV 160 315
8.17 Current characteristics      
8.18 Rated current in continuous service (In) A 3150 3150
8.19 Rated short-time cutter (Ikh) kA 40 40
8.20 Duration of the short-circuit assigned (t) s 4 4
8.21 Peak value of the permissible current (Ip) kAp 100 100
8.22 Bus transfer current   2500 2500
8.23 Nominal transfer current of bars A 1600 1600
8.24 Nominal transfer voltage of bars V 30 30
8.25 Mechanical operations of the disconnector   2000 2000
8.26 Class of earthing disconnector      
8.27 Control device      
8.28 a) Operation   yes yes
8.29 b) Type of operating mechanism   Electric mechanism Electric mechanism
8.30 c) Manual   yes yes
8.31 d) Electric (local and remote)   yes yes
8.32 e) REMOTE-DISCONNECTED-LOCAL selector   yes yes
8.33 Auxiliary voltage for closing and opening control      
8.34 a) Substation  named "CALLALI" Vcc 110 110
8.35 Auxiliary voltage operating mechanism      
8.36 a) Substation  named "CALLALI" V 110 110
8.37 Number of reserve auxiliary contacts      
8.38 a) Opening of the end of career   8 8
8.39 b) End of career closing   8 8
8.40 c) On the move   yes yes
8.41 Degree of protection of the operating mechanism in accordance with IEC 60947 - 1   yes yes
9  CURRENT TRANSFORMER IN BUSHING FOR MEASUREMENT AND PROTECTION
9.01 Rules   IEC 60044 IEC 60044
9.02 Type of installation   Exterior Exterior
9.03 Kind   Toriodal Toriodal
9.04 Voltage characteristics      
9.05 System Voltage kV 66 132
9.06 Nominal voltage of the equipment kV 72.5 145
9.07 Rated voltage supported at industrial frequency (Ud) kV 140 275
9.08 Assigned voltage supported to the interior lightning impulse (Up) of the Hybrid Bay kV 325 650
9.09 Assigned frequency (fr) Hz 50/60 50/60
9.10 Current characteristics      
9.11 Primary current assigned (Ion) A 300-600 300-600
9.12 Rated secondary current (Isn) A 5 5
9.13 Rated thermal short-circuit current (Ith) kA 40 40
9.14 Measure   0,2 0,2
9.15 Conventional protection   5P 5P
9.16 Characteristics cores   ELECTROMAGNETIC ELECTROMAGNETIC
9.17 a) Allocated transformation ratio A 650 650
9.18 b) Relationship for which the specification must comply A 300-600/5 300-600/5
9.19 c) Precision class   0,2 0,2
9.20 d) Precision loading VA 15 15
9.23 a) Allocated transformation ratio A 300-600/5 300-600/5
9.24 b) Relationship for which the specification must comply A 300-600/5 300-600/5
9.25 c) Precision class VA 20 20
9.26 d) Precision loading   5P 5P
9.27 e) Precision limit factor   20 20







 
TECHANICAL SPECIFICAITON DATA SHEET 
        M00  72.5KV/145KV PASS PLUG AND SWITCH SYSEM
ITEM  DESCRIPTION UNIT 72.5KV 145KV
1 GENERAL SERVICE CONDITIONS
1.01 Installation type   Indoor/Outdoor Indoor/Outdoor
1.02 Altitude above sea level    ≤1000M ,Adjuatable to 5000m ≤1000M,adjustable to 5000m
1.03 Standard   IEC 62271 IEC62271
1.04 Extinction medium   SF6 SF6
1.05 Maximum ambient air  temperature °C (+40ºC) (+40ºC)
1.06 Minimum ambient air temperature  °C (-30ºC) (-30ºC)
1.07 Relative humidity % ≤100%  day average  ,≤95% month average ≤100%  day average  ,≤95% month average
1.08 Wind pressure (wind speed not more than 34m/s) Pa 700 700
1.09 Solar radiation according to IEC 894 W/m2 <1000 <1000
1.10 Seismic acceleration according to IEC 1166 g >0.5 horizontal,>0.25 vertical  >0.5 horizontal,>0.25 vertical
1.11 Degree of protection according to IEC 60529 IP class 44 44
1.12 Pollution level according to IEC 60815   IV IV
1.13 Anti-corrosion of tank   Yes Yes
1.14 Ice Thickness mm 10 10
2 Weight of Equipment
2.01 SBB Module Kg 2330 2620
2.02 SBB Support frame  Kg 150 150
2.03 SBB Conntrol Panel Kg 80 80
2.04 SBB SF6 Gas Kg 40 50
2.05 Total weight of SBB PASS Kg 2600 2900
3 Surface Finishing 
3.01 Support structure(Hot-dip galvanised  according to DIN50976) um 85 85
3.02 Surface painting    NO NO
4 Electrical Data 
4.01 Number of poles   2 2
4.02 Number of phases   3 3
4.03 Type of execution   Outdoor Outdoor
4.04 Assigned frequency (fr) Hz 50/60 50/60
4.05 Voltage Characteristics      
  Nominal voltage of the system kV 66 132
  Maximum equipment voltage kV 72.5 145
4.06 Level of insulation      
  Rated voltage supported at industrial frequency (Ud)(1min) kV    
  To ground kV 140 275
  Across the isolating distance  kV 160 315
  Assigned voltage supported to the lightning impulse (peak)      
  to ground kV 325 650
  across the isolating distance  kV 375 750
5 Bushing 
5.01 BIL exterior of Bushing kV 375 750
5.02 Interior BIL of Bushing kV 325 650
5.03 Bushing Materual   Porcelain/Composite Porcelain/Composite
5.04 Rated voltage kV 72.5 145
5.05 Rated Current  A 3150 3150
5.06 Rated power frequency withstadn voltage  kV 140 275
5.07 Rated light impulse withstand voltage kV 325 650
5.08 Maximum dynamic current kAp 100 100
5.09 Duration of the short-circuit assigned (tk) s 4 4
5.10 Patial discharge level 46kV pC at 46kv ≤5 at 58kv≤5
5.11 Radi inerference Voltage level Uv ≤2500 ≤2500
5.12 Power frequency withstand voltage (15min) at 100Kpa /20ºC   46 58
5.13 Arcing distance mm 800 1452
5.14 Creepage distance mm 2250 4500
5.15 Forces that act on the concrete bases during the operation      
5.16 a) Vertical N 1250 1250
5.17 b) Horizontal N 750 750
5.18 c) transversal N 1000 1000
6 DIMENSIONS      
6.01 A) hIGH mm 3700 4500
6.02 b) Wide mm 2400 4100
6.03 c) Length mm 2700 2700
7 CIRCUIT BREAKER
7.01 Standard      IEC 52271-100 IEC 52271-100
7.02 Type   three-phase three-phase
7.03 Extinction medium Gas SF6 SF6
7.04 Number of poles   3 3
7.05 Number of cameras per pole   1 1
7.06 Type of installation   Outdoor Hybrid bay Outdoor Hybrid bay
7.07 Assigned frequency (fr) Hz 50/60 50/60
7.08 Tension characteristics      
7.09 System Voltage kV 66 132
7.10 Nominal voltage of the equipment kV 72.5 145
7.11 Rated voltage supported at industrial frequency (Ud) phase-phase, phase-earth and through open switch kV 140 315
7.12 Assigned voltage supported to the impulse type ray (Up) phase-ground, between phases and through open switch   325 650
7.13 BIL interior (inner) kV 325 650
7.14 Current characteristics      
7.15 Rated current in continuous service (Ir) A 3150 3150
7.16 Rated short-circuit current (Ics) kA 40 40
7.17 Short circuit current assigned (Ip) kAp 100 100
7.18 First pole factor   1.5 1.5
7.19 Rated short-circuit duration (tk) s 3 3
7.20 Assigned sequence of maneuvers O-0, 3s-CO-3min-CO   yes yes
7.21 Number of mechanical operations TIMES 6000 6000
7.22 Pole discrepancy logic   yes yes
7.23 Anti-pumping device   yes yes
7.24 CHARACTERISIC FOR TERMINAL FAULT (ACCORD TO IEC62271-100)
7.25 Short circuit breaking current  KA 40 40
7.26 Short circuit making  current  KA 100 100
7.27 Recovery voltage KV 63 86
7.28 TRV Peak value  KV 124 171
7.29 Rate of rise of recovery voltage (RRRV) KV/US 1.47 2
7.30 OPENING TIME (AT RATED VOLTAGE)   32 32
7.31 CLOSING TIME(AT RATED VOLTAGE)   85 85
7.32 MINIMUM ARCING TIME MS 7 7
7.33 MINIMUM CLEARING ARCING TIME MS 50 50
7.34 MAXIMUM BREAK TIME   60 60
7.35 PEAK CURRENT VALUE RATED TO PEAK VALUE FOR SYMMETRICAL SHORT CIRCUIT CURRENT  PU 1.21 1.21
7.36 DURATION OF MAJOR LOOP MS 11.5 11.5
7.37 CHARACTERISTIC FOR SHORT LINE FUALT (L90 DUTY CYCLS TO IEC62271-100)
7.38 Short line fault current    36 36
7.39 TIME DELAY    2 2
7.40 TRV SIURCE CHARACTERISTICS      
7.41 TRV PEAK VALUE Uc   144 144
7.42 Time to reach peak t3      
7.43 Rated of rise of recovery voltage (RRRV)   2 2
7.44 CHARACTERITIC FOR OUR OF PHASE MAKING AND BREAKING ACCORDING TO IEC62271-100
7.45 Out of phase breaking current    10 10
7.46 out of phase voltage factor    2.5 2.5
7.47 CHARACTERISTIC FOR CAPACITIVE CURRENT SWITCHING (LC1 LC2 ACCORDING TO 62271-100)
7.48 RATED LINE CHARGING BREAKING CURRENT  A 50 50
7.49 RATED CABLE CHARGING BREAKING CURRENT  A 160 160
7.50 VOLTAGE FACTOR K PU 2 2
7.51 Auxiliary voltage for heating and lighting V 220 220
7.52 Number of reserve auxiliary contacts      
7.53 a) Opening   10 10
7.54 b) Closing   10 10
7.55 Closing and opening devices      
7.56 a) Supply DC voltage assigned (Ua) Vcc 110 110
7.57 b) Number of opening coils per mechanism   2 2
7.58 c) Number of closing coils per mechanism   1 1
7.59 d) Consumption of the closing coil W 253 253
7.60 e) Consumption of the opening coil W 297 297
7.61 f) Opening coil voltage range % 60-120 60-120
7.62 g) Voltage margin of closing coil % 85-110 85-110
7.63 Operation counter by mechanism   yes yes
7.64 Data of the operation mechanism      
7.65 a) Type   SPRING SPRING
7.66 b) Consumption for closing W 3000 3000
7.67 c) Consumption for opening W 1700 1700
7.68 d) Voltage margin for normal operation of the mechanism V 26.4 26.4
7.69 e) Degree of protection in accordance with IEC 60947 - 1   yes yes
7.70 f) REMOTE-DISCONNECTED-LOCAL switch   yes yes
7.71 Alarms and indicators      
7.72 a) Low gas pressure (two states)   yes yes
7.73 b) Fault in the control device   yes yes
7.74 c) Pole discordance   yes yes
7.75 d) Position local / remote status control box   yes yes
7.76 e) Spring distension   yes yes
7.77 f) Terminal monitoring trip coils   yes yes
7.78 Mechanism engine data      
7.79 a) Type   Electric Electric
7.80 b) Tension Vcc 110 110
7.81 c) Power W 400 400
7.82 d) Operation counter yes / no   yes  yes 
7.83 e) Excessive operation indication yes / no   no no
7.84 f) Operating voltage margin % 10 10
7.85 Nominal motor current A 3,5 +/- 1,5 3,5 +/- 1,5
7.86 Inrush current A 10 +/- 1,5 10 +/- 1,5
8 DISCONNECTOR      
8.01 Model   yes yes
8.02 Standarda   IEC 62271-102 IEC 62271-102
8.03 Type of installation   Outdoor Outdoor
8.04 Type of operation   three phase three phase
8.05 Number of combined switches   1 1
8.06 Type of connection disconnector construction   Compressed air Compressed air
8.07 Assigned frequency (fr) Hz 50/60 50/60
8.08 Tension characteristics   Single pressure Single pressure
8.09 System Voltage kV 66 132
8.10 Rated voltage of the equipment kV 72.5 145
8.11 Assigned voltage supported to the lightning impulse (Up), inside the Hybrid Bay      
8.12 a) On land and between poles kV 325 650
8.13 b)      A través de la distancia de seccionamiento kV 375 750
8.14 Rated voltage supported at the industrial frequency (Ud) kV 72.5 145
8.15 a) On land and between poles kV 140 275
8.16 b) Through the sectioning distance kV 160 315
8.17 Current characteristics      
8.18 Rated current in continuous service (In) A 3150 3150
8.19 Rated short-time cutter (Ikh) kA 40 40
8.20 Duration of the short-circuit assigned (t) s 4 4
8.21 Peak value of the permissible current (Ip) kAp 100 100
8.22 Bus transfer current   2500 2500
8.23 Nominal transfer current of bars A 1600 1600
8.24 Nominal transfer voltage of bars V 30 30
8.25 Mechanical operations of the disconnector   2000 2000
8.26 Class of earthing disconnector      
8.27 Control device      
8.28 a) Operation   yes yes
8.29 b) Type of operating mechanism   Electric mechanism Electric mechanism
8.30 c) Manual   yes yes
8.31 d) Electric (local and remote)   yes yes
8.32 e) REMOTE-DISCONNECTED-LOCAL selector   yes yes
8.33 Auxiliary voltage for closing and opening control      
8.34 a) Substation  named "CALLALI" Vcc 110 110
8.35 Auxiliary voltage operating mechanism      
8.36 a) Substation  named "CALLALI" V 110 110
8.37 Number of reserve auxiliary contacts      
8.38 a) Opening of the end of career   8 8
8.39 b) End of career closing   8 8
8.40 c) On the move   yes yes
8.41 Degree of protection of the operating mechanism in accordance with IEC 60947 - 1   yes yes
9  CURRENT TRANSFORMER IN BUSHING FOR MEASUREMENT AND PROTECTION
9.01 Rules   IEC 60044 IEC 60044
9.02 Type of installation   Exterior Exterior
9.03 Kind   Toriodal Toriodal
9.04 Voltage characteristics      
9.05 System Voltage kV 66 132
9.06 Nominal voltage of the equipment kV 72.5 145
9.07 Rated voltage supported at industrial frequency (Ud) kV 140 275
9.08 Assigned voltage supported to the interior lightning impulse (Up) of the Hybrid Bay kV 325 650
9.09 Assigned frequency (fr) Hz 50/60 50/60
9.10 Current characteristics      
9.11 Primary current assigned (Ion) A 300-600 300-600
9.12 Rated secondary current (Isn) A 5 5
9.13 Rated thermal short-circuit current (Ith) kA 40 40
9.14 Measure   0,2 0,2
9.15 Conventional protection   5P 5P
9.16 Characteristics cores   ELECTROMAGNETIC ELECTROMAGNETIC
9.17 a) Allocated transformation ratio A 650 650
9.18 b) Relationship for which the specification must comply A 300-600/5 300-600/5
9.19 c) Precision class   0,2 0,2
9.20 d) Precision loading VA 15 15
9.23 a) Allocated transformation ratio A 300-600/5 300-600/5
9.24 b) Relationship for which the specification must comply A 300-600/5 300-600/5
9.25 c) Precision class VA 20 20
9.26 d) Precision loading   5P 5P
9.27 e) Precision limit factor   20 20