Certification: ISO9001
Shell Material: Steel Plate
Voltage Level: 6kv/15kv/27kv/38kv
Installation: Fixed
Structure: Cabinet
Current: AC
Customization:
Gold Member Since 2017

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company, Group Corporation

Basic Info.

Model NO.
KYN
Transport Package
Wooden
Specification
15KV/27KV/38KV, 50HZ/60HZ,
Trademark
HEMG
Origin
China
Production Capacity
50000PCS

Product Description

Summary
HKYN61-33KV Type Removable AC Metal-clad Switchgear (short for HKYN61) is complete set distributing equipment for 33kV, 3 phase, 50Hz single bus-bar and single bus-bar section system. It main used for electric power network used as receiving and distributing power energy and also for control,monitor,and protection.
The main switch adopts HZN85-33 Vacuum circuit breaker or Schneider SF series,ALSTOM FP series SF6 circuit breaker, have the advantages such as compact structure,superior performance,high reliability.
HKYN61 meet IEC298,GB3906-91 standard, have the "five Prevention" function,high structural strength,Component arrangement reasonable,have complete scheme,can extensible, is a ideal new type distributing equipment.


1.     Service Conditions
   a. The ambient air temperature: +40ºC to -15ºC.
b. Altitude ≤ 4500 M
c. The relative humidity :
Daily average value is not more than 95%
Monthly average value is not more than 90%
d. The earthquake intensity does not exceed  8 degrees,
f. Around air isn't polluted by corrosive or combustibility gas,Vapor.
If the service conditions of products is not under above conditions, it will be negotiated by user and manufacture.
2.     Technical data and requirement
2.1 Technical data for KYN61
No Item Unit Data
1 Rated voltage kV 33KV
2 Rated frequency Hz 50/60
3 Rated current of the main bus-bar A 630,1250,1600,2000
4 Rated current of the branch bus-bar A 630,1250,1600,2000
5 Rated insulation level 1 min Power frequency withstand voltage kV Phase to phase
Phase to earth
Primary insulation breakers
95 115
Lighting impulse withstand voltage 185 215
1 min Power frequency withstand voltage for auxiliary Control circuit V 2000
6 Rated Short circuit breaking current KA 25, 31.5
7 Rated short circuit making current (peak) kA 63, 80
8 Rated short-time peak withstand current kA 63, 80
9 4 S short-time withstand current kA 25, 31.5
10 Power frequency withstand voltage for auxiliary Control circuit V 110 ,≈220
11 Protecting level   Enclosure IP 4X, Compartments IP2X
12 Dimension (W*D*H) mm 1200 or 1400*2800*2600
 
2.2 Technical Data for ZN85-40.5 Vacuum Circuit Breaker
No Item Unit Data
1 Rated voltage kV 33KV
2. Rated frequency Hz 50/60
3 Rated insulation level I min power frequency withstand voltage  
 
kV
95
lightning impulse withstand voltage (peak) 185
4 Rated current A 630 1250 1600 2000
5 Rated short-time withstand current kA 25  31.5
6 Rated peak withstand current kA 63   80
7 Rated short circuit duration time s 4
8 Rated short circuit Breaking Current kA 25   31.5
9 Prospective transient recovery voltage kV With GB1984
10 Rated short circuit Making Current kA 63  80
11 Open-close rated capacitor bank current A 400  630
12 Rated operation sequence   0-0.3s-CO-180s-co
13 Rated short circuit breaking current breaking times Times 20
14 Opening time ms 35~60
15 Closing time ms 40~80
16 Mechanical life Times 10000
17 Open distance of contact mm 18~22
18 Over travel mm 6±1
19 Contact allowed wear thickness mm 3
20 Average closing speed m/s 0.6~0.9
21 Average opening speed (run 10mm) m/s 1.6~2.0
22 Contact closing bounce time ms 2
23 Three phase contact opening asynchronism ms 2
24 Three phase contact closing asynchronism ms 2
25 Every phase circuit DC resistance 60
26 Rated contact spring pressure under closing condition N 3100
 
2.3  Technical Data for Schneider SF Type and ALSTOM series SF6 circuit break
No Item Unit Data
1 Rated voltage kV 33
2. Rated frequency Hz 50
3 Rated insulation level I min power frequency withstand voltage  
 
kV
95
lightning impulse withstand voltage (peak) 185
4 Rated current A 630 1250 2000
5 Rated short-time withstand current kA 25  31.5
6 Rated short-time duration time s 3
7 Rated short circuit Breaking Current kA 25   31.5
8 Rated short circuit Making Current kA 63    80
9 Open-close rated capacitor bank current A 400~1750
12 Rated operation sequence   0-0.3s-CO-180s-co
O-180s-CO-180s-CO
13 Rated short circuit breaking current breaking times Times 20
14 Opening time ms 45±4 (SF) 65 (FP)
15 Closing time ms 68±4 (SF) 70 (FP)
16 Mechanical life Times 10000
 
2.4  Technical data and Accurate grade combination for LZZB9-35 Current Transformer
Primary current(A)  Accurate grade combination Rated output {COS¢=0.8(lag), (VA)} Rated short time thermal current (kA) Short time dynamic stability current  (kA)
0.2 0.5 10P/10 10P15 10P20
30-100 0.2/10P10
0.2/10P15
0.2/10P20
0.5/10P10
0.5/10P15
0.5/10P20
 
15 30 50 30 20 150 Iin 375 Iin
150 31.5 80
200 44.5 80
300-500 15 30 50 30 20 54.5 80
600-800 30 50 50 40 30 63 80
1000-2000 40 50 50 50 30 80 100
 
2.5 Technical data and Accurate grade combination for LDBJ8-40.5 contact type current transformer.
Primary current(A)  Accurate grade combination and the corresponding rated output Rated short time thermal current (kA) short time dynamic stability current  (kA)
0.2/10P10 0.5/10P10 0.2/0.5 10P10/10P10
5-300 10/30 20/30 10/20 20/20 150 Iin 2.5 Iin
400 10/40 15/40 10/15 20/20 63 160
500 10/40 15/40 10/15 25/25 63 160
600 10/50 30/50 10/30 30/30 63 160
750-800 20/50 30/50 20/30 30/30 63 160
1000-1500 30/50 50/50 30/50 40/40 80 180
2000-3150 30/50 50/50 50/50 50/50 100 180
2.5   Technical data for JN22-40.5 Earth Switch
No Item Unit Data
1 Rated voltage kV 33
2 Rated insulation level I min power frequency withstand voltage  
 
kV
85
lightning impulse withstand voltage (peak) 95
3 4s short-time withstand current kA 31.5
4 Rated peak withstand current(peak) kA 80
5 Rated short circuit Making Current (peak) kA 80
 
3,Structure
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Scheme No 01 02 03 04
Main connecting diagram        
Main electrical
element
Circuit Breaker ZN85/SF/FP 1 1 1 1
Earth switch JN22-33 1 1 1 1
CT- LZZB9-33   1 2 3
Electric Display DSN6-33   1 1 1
         
Function Overhead entry (out) Overhead entry (out) Overhead entry (out) Overhead entry (out)
Note  
 
 
Scheme No 05 06 07 08
Main connecting diagram        
Main electrical
element
Circuit Breaker ZN85/SF/FP 1 1 1 1
Earth switch JN22-33 1 1 1 1
CT- LZZB9-33   1 2 3
Electric Display DSN6-33 1 1 1 1
         
Function Cable entry (out) Cable entry (out) Cable entry (out) Cable entry (out)
Note  
 
 
 
 
 
 
 
Scheme No 09 10 11 12
Main connecting diagram        
Main electrical
element
Circuit Breaker ZN85/SF/FP 1 1 1 1
CT- LZZB9-33   1 2 3
         
         
         
Function Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Note  
 
 
 
Scheme No 13 14 15 16
Main connecting diagram        
Main electrical
element
CT- LZZB9-33 1 1 2 3
         
         
         
         
Function Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Right(left)
connectiong
Note  
 
 
 
 
 
 
 
Scheme No 17 18 19 20
Main connecting diagram        
Main electrical
element
CT- LZZB9-33   1 2 3
Earth switch JN22-33 1 1 1 1
Electric Display DSN6-33 1 1 1 1
         
         
Function Cable Entry (out) Cable Entry (out) Cable Entry (out) Cable Entry (out)
Note  
 
 
 
 
Scheme No 21 22 23 24
Main connecting diagram        
Main electrical
element
CT- LZZB9-33   1 2 3
Earth Switch JN22-33 1 1 1 1
Electric Display DSN6-33 1 1 1 1
         
         
         
Function Cable Entry (out) Cable Entry (out) Cable Entry (out) Cable Entry (out)
Note  
 
 
 
 
 
Scheme No 25 26 27 28
Main connecting diagram        
Main electrical
element
Circuit Breaker ZN85/SF/FP 1 1 1 1
CT-LDBJ8-33 (Q) 1 2 3 1
CT- LZZB9-33 1 2 3 1
Earth switch JN22-33 1 1 1 1
Electric Display DSN6-33 1 1 1 1
Function Overhead entry (out) Overhead entry (out) Overhead entry (out) Cable entry (out)
Note  
 
 
 
Scheme No 29 30 31 32
Main connecting diagram        
Main electrical
element
Circuit Breaker ZN85/SF/FP 1 1    
CT-LDBJ8-33(Q) 2 3 1 2
CT- LZZB9-33 2 3 1 2
Earth switch JN22-33 1 1 1 1
Electric Display DSN6-33 1 1 1 1
Function Cable Entry (out) Cable Entry (out) Overhead Entry (out) Overhead Entry (out)
Note  
 
 
 
 
 
 
 
 
 
 
Scheme No 33 34 35 36
Main connecting diagram        
1Main electrical
element
CT-LDBJ8-33 (Q) 3 1 2 3
CT- LZZB9-33 3 1 2 3
Earth switch JN22-33 1 1 1 1
Electric Display DSN6-33 1 1 1 1
         
Function Overhead Entry (out) Cable Entry (out) Cable Entry (out) Cable Entry (out)
Note  
 
 
 
 
Scheme No 37 38 39 40
Main connecting diagram        
1Main electrical
element
Voltage Transformer JDZX9-33 3 1 2 3
Fuse XRNP-33 3 1 2 3
Surage arrest HY5WZ-51/134 1 1 1 1
  1 1 1 1
         
Function Overhead Entry (out) Cable Entry (out) Cable Entry (out) Cable Entry (out)
Note  
 
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
6kv/12kv/15kv/24kv/38kv, 50Hz/60Hz, Indoor 50Hz/60Hz PCM Protection and Control Vacuum/Sf6 Gas /Switchgear Panel
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now