Breaking Capacity: | 25ka, 31.5ka |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Fixed |
Structure: | ACB |
Customization: |
---|
Suppliers with verified business licenses
Technical Specifications
|
|
|
|
|
|
|||||
NO
|
Item
|
|
|
Unit
|
Value
|
|||||
1
|
Rated voltage
|
|
|
KV
|
40.5
|
|||||
2
|
Rated insulation level
|
Power frequency withstand voltage
|
Dry test
|
|
95
|
|||||
|
|
|
Wet test
|
80
|
|
|||||
|
|
Lightning impulse withstand voltage (peak)
|
|
185
|
|
|||||
3
|
Rated current
|
|
|
A
|
125,016,002,000
|
|||||
4
|
Rated short-circuit breaking current
|
|
|
KA
|
20,25,31.5
|
|||||
5
|
Rated operation sequence
|
|
|
|
0-0.3s-combination-180s-combination
|
|||||
6
|
Rated short circuit current breaking times
|
|
|
times
|
12
|
|||||
7
|
Rated short circuit closing current (peak)
|
|
|
KA
|
50,63,80
|
|||||
8
|
Rated peak withstand current
|
|
|
|
|
|||||
9
|
Rated short-time withstand current
|
|
|
KA
|
20,25,31.5
|
|||||
10
|
Rated short circuit continuous current
|
|
|
S
|
4
|
|||||
11
|
Average opening speed
|
|
|
m/s
|
1.5±0.2
|
|||||
12
|
Average closing speed
|
|
|
0.7±0.2
|
|
|||||
13
|
Contact closing bounce time
|
|
|
s
|
≤2
|
|||||
14
|
Three-phase combined (minute) gate synchronous time difference
|
|
|
≤2
|
|
|||||
15
|
Closing time
|
|
|
≤150
|
|
|||||
16
|
Opening time
|
|
|
≤60
|
|
|||||
17
|
Mechanical life
|
|
|
times
|
10000
|
|||||
18
|
Rated operating voltage and auxiliary circuit rated voltage
|
|
|
V
|
DC220,110,24
|
|||||
|
|
|
|
|
AC220,110,24
|
Suppliers with verified business licenses