Product overview:
XGN15-12(F), HXGN15-12(F·R) box type fixed AC metal closed switchgear (hereinafter referred to as "switchgear"), used in the rated voltage 12kV, rated current 630A and below the ring grid power supply or radiation power supply system, especially suitable for pre-installed substation as the control and protection of power system. This product is equipped with FLN36-12D type sulfur hexaoxide load switch or FLRN36-12D type load switch-dissolver combination electrical appliance, which has the characteristics of small size, light weight, easy operation, light operation force, reliable interlocking, maintenance-free and so on. It is a new generation of high-voltage switchgear required for urban power grid transformation and construction.
This product conforms to: GB3906 "3~35kV AC metal closed switchgear", GB/T11022 "high voltage switchgear and control equipment standard common technical requirements",IEC298 "rated voltage 1kV Above 50kV and below AC metal closed switchgear and Control Equipment ",DI/T404 "Indoor AC High voltage Switchgear ordering Technical Conditions" standards.
Main Technical specifications Serial number of the main technical specifications of the switch cabinet
Applicable conditions:
1 Ambient air temperature:-15ºC~+40ºC
2 Altitude :1000m and below,
3 Humidity Case:
The daily mean value is not more than 95%, and the daily mean value of water vapor pressure is not more than 2.2kPa;
The monthly mean value is not more than 90, and the monthly mean steam pressure is not more than l.8kPA.
4 Seismic intensity,not more than 8 degrees.
5 There is no obvious pollution such as turbid or combustible gas.
Note: Users may negotiate with the Company when the above normal conditions of use are exceeded.
structure:
Switchgear is composed of cabinet, main switch (SF6 load switch or combined appliance),ground switch, instrument room,bus and other electrical components and auxiliary components.
The cabinet body is made of aluminum zinc steel plate by modular forming assembly. The backside of the cabinet is provided with a pressure relief channel to protect the operator in case of internal
faiture.The bus in the bus room is covered with insulation and directly connected to the wiring terminals of the load switch. The three phase bus is arranged longitudinally, so that the switchgear can be arbitrarily extended from left to right and easy to change its layout.The instrument room is located in the upper part of the switching equipment,which can be equipped with ammeter,voltmeter,indicator light and electric operating mechanism.
Technical Parameters:
Main Technical specifications Serial number of the main
Number |
Name |
Unit |
HXGNl5-12 (F) |
HXGNl5-12 (F·R) |
1 |
Rated voltage |
V |
12 |
12 |
2 |
Ratec frequency Rated |
Hz |
50 |
50 |
3 |
Main busbar rated current |
A |
630 |
630 |
4 |
Maximum rated current of fuse |
A |
- |
125 |
5 |
The main circuit is rated for short-time current tolerance/
Rated short circuit duration |
KA/S |
20/3 |
20/3 |
6 |
Rated expected short-circuit breaking current |
KA |
- |
50 |
7 |
1min
power frequency withstand voltage ,phase to phase,to earth |
KV |
42/48 |
42/48 |
8 |
Ground shock withstand voltage ,phase to phase,to earth |
KV |
75/85 |
75/85 |
9 |
level of protection |
|
IP2X |
IP2X |
Main switch inside switchgear(SF6 load switch and combined appliance
)technical specification
Number |
Name |
Unit |
HXGNl5-12 (F) |
HXGNl5-12 (F·R) |
1 |
The ground circuit is rated as a short-time tolerant current source |
KA/s |
20/2 |
20/2 |
2 |
Rated peak tolerable current &
Rated short-circuit closing current |
KA |
50 |
125 |
3 |
Main busbar rated current |
A |
630 |
630 |
4 |
Maximum rated current of fuse |
A |
630 |
630 |
5 |
The main circuit is rated for short-time current tolerance/
Rated short circuit duration |
A |
31.5 |
31.5 |
6 |
Rated expected short-circuit breaking current |
A |
10 |
10 |
7 |
1min
power frequency withstand voltage ,phase to phase,to earth |
KVA |
- |
1250 |
8 |
Ground shock withstand voltage ,phase to phase,to earth |
A |
- |
1700 |
9 |
level of protection |
time |
2000 |
2000 |
About US: