VS-JB900 6 Phase Current Output Microcomputer Protection Relay Test Set From China Supplier Technique parameters
1. AC current source Current range: 6x (0~30A)/phase, accuracy 0.5%. 6 phase parallel current output: 180A Phase current working value for allowed long time: 10A Power: 300VA/phase Maximum output power of 6 phases in parallel: 900VA Maximum permitted work time of 6 phases in parallel: 10S Frequency range: 0~1000Hz; accuracy: 0.001Hz Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1° 2. DC current source Current range: 20A / phase, power: 300VA/phase, accuracy:0.5% 3. AC voltage source Phase voltage output:6x( 0~125V)/phase, accuracy: 0.5% Line voltage output: 0~250V Phase voltage / Line voltage output power: 70VA / 100VA Frequency range: 0~1000Hz accuracy: 0.001Hz Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1° 4. DC voltage source Phase voltage output range: 0~±150V accuracy: 0.5% Line voltage output range: 0~±300V Phase voltage / Line voltage output power: 90VA / 180VA 5. Switch terminal Switch input terminals: 8 pairs Dead contact: 1-20mA, 24V active output inside the device. Potential flip: 0--6V DC low level 15-250V DC high level Switch output terminals: 4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A 6. Time measurement range Range: 1ms-9999s; accuracy: 1ms 7. Dimension & weight Dimension: 455 (mm)×530 (mm)×220 (mm) Weight: 30Kg. 8. Power AC220V±10% 50Hz 15A