Basic Info.
Model NO.
ydc3310-ydc3380
Classification
Lighting/Power
Standby UPS
Sine Wave Output UPS
Topology
Double-Conversion Online UPS
Input Power Factor
>0.99 Typical
Display
Graphical LCD with Blue Backlight
Communication Ports
(1) RS-232, (1) USB, (1) Epo
Communication Slots
Mini-Slot Communication Bays
Input Current Distortion
≤5% Thd
UPS Bypass
Automatic on Overload or UPS Failure
Parallel Technology
Powerware Hot Sync® Technology
Specification
500 x 710 x 960
Product Description
YDC10-80kVA
KSTAR YDC3310-YDC3380 series online double conversion UPS System adopts advanced DSP control and N+X redundancy design to enhance the reliability. With high power factor (PF) and ECO mode operation for energy saving, UD series is the cost-effective choice in the industry. It has been widely used for server rooms, personal computers, data warehouses, medical clinics, industrial application and office facilities.
General Features
True double-conversion
Real-time digital signal processor (DSP) control
N+X parallel redundancy
Selectable quantity of battery for each group:for long run unit
Adjustable charging current via LCD
3-stage charging design optimizes battery performance
ECO mode operation for energy saving
Self-diagnosis at startup
Emergency power off function(EPO)
Maintenance bypass is convenient for maintenance
Generator compatible
Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
Cold start
Technical Specification
MODEL | YDC3310 | YDC3315 | YDC3320 | YDC3330 | YDC3340 | YDC3360 | YDC3380 |
Capacity (VA/Watts) | 10K / 9K | 15K / 13.5K | 20K / 18K | 30K / 27K | 40K / 36K | 60K / 54K | 80K / 72K |
INPUT | |
Nominal Voltage | 380/400/415Vac(3Ph+N+PE) |
Operating Voltage Range | 208~478Vac@half load; 305~478Vac@full load |
Operating Frequency Range | 50Hz:45~55Hz,60Hz:54~66Hz |
Power Factor | ≥0.99 |
| Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) |
Bypass Voltage Range | 230V:+20%(Optional +10%,+15%) |
| 240V:+15%(Optional +10% ) |
| Min. voltage: -45% (Optional -10%, -20%,-30%) |
ECO Range | Same as bypass |
Harmonic Distortion (THDi) | ≤3%(100% non-linear load) |
OUTPUT | |
Output Voltage | 380/400/415Vac(3Ph+N+PE) |
Power Factor | 0.9 |
Voltage Regulation | ±1% |
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) |
Bat. Mode | 50/60(1±0.1%)Hz |
Crest Factor | 3:01 |
Harmonic Distortion (THDv) | ≤2% with linear load |
≤5% with non-linear load |
Waveform | Pure Sinewave |
Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms |
EFFICIENCY | |
Efficiency | 95% |
BATTERY | |
Battery | Standard unit | ±120Vdc (20pcs 12V9AH) | ±120Vdc (2x20pcs 12V9AH) | ±120Vdc (3x20pcs 12V9AH) | N/A |
Voltage | Long run unit | Selectable Voltage:±96V/±108V/±120Vdc | Selectable Voltage:±192V/±204V/±216V/ ±228V/±240Vdc |
Charging | Standard unit | 1.35 | 2.7 | 4.05 | N/A |
Current (A) | Long run unit | Max.current 10A | Max.current 15A | Max.current 30A |
PROTECTI | ON | |
| Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately |
Overload | Bat. Mode | Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last 5S, ≥150% shut down UPS immediately |
| Bypass Mode | 20A(Input breaker) | 32A(Input breaker) | 40A(Input breaker) | 63A(Input breaker) | 80A(Input breaker) | 100A(Input breaker) | 125A(Input breaker) |
Short Circuit | Hold Whole System |
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Battery Low | Alarm and Switch off |
INDICATORS | |
Audible & Visual Alarms | Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD Display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
Parameters On The LCD Panel | Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time |
MANAGEMENT | |
Communication Interface | RS-232,RS-485,USB,Parallel card, SNMP card(Optional), Relay card (Optional),Battery temperature sentor(optional) |
ENVIRONMENT | |
Operating Temperature | 0~40ºC |
Storage Temperature | -25~55ºC |
Humidity Range | 0~95% (Non-condensing) |
Altitude | < 1500m |
Noise Level | <55dB | <58dB | <63dB |
PHYSICAL | |
Dimension W×D×H (mm) | 250×828×868 | 360×828×868 |
Net Weight (kg) | 115/57 | 170/63 | 171/64 | 223/71 | 73 | 118 | 122 |
STANDARDS | |
Noise Suppression | Complies with EN62040-2 |
Safety | IEC/EN62040-1,IEC/EN60950-1 |
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, |
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
Address:
1st Floor 38 Building Ai Lian Industrial Park Longgang District ShenZhen China
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics, Industrial Equipment & Components
Management System Certification:
ISO 9001, ISO 9000, ISO 14001
Company Introduction:
As a manufacturer specializes in the development, manufacturing, management and after-sales services of uninterruptible power supply (UPS) products, Shenzhen Gene Power Tech. Co., Ltd. Has created an excellent technical team, and the core members of the team have accumulated more than sixteen years of experience in the development and production of UPS.
We strictly control the quality of electronic components and parts for each supplier, optimize the manufacturing process and strictly manage the production process to provide customers with quality UPS products. We will always follow this basic principle to serve the customers.
Our products have been sold to customers at home and abroad. Relying on good faith, dedication, profession, efficiency, high quality, and speedy service, we have won the trust and confidence of customers.
At present, we have three mature product series, namely Prome, Mini 3P3, and Mini module; Please refer to the catalog for all the product types of each series, as well as the detailed product information. In addition, we can also provide customers with customized products of special specifications. Please feel free to contact us!