Task: | Program |
---|---|
Structure: | Combination |
Signal: | Continuous |
Function: | Automatic Control |
Certification: | RoHS, ISO: 9001, CE |
Condition: | New |
Customization: |
---|
Suppliers with verified business licenses
Order Data
Products data |
Order No. |
|
CTSC-200 V5 series CPU |
||
CPU226I V5 version |
CPU226I:72KB program memory/110KB data memory,220VAC power supply,24DI/16DO relay output,2A,2*PPI/FPORT,1*Ethernet port,data permanent storage when power-down,support analog expansion board,CAN expansion board and RS485 expansion board. |
CTS7 216-2BD45-0X40 |
Performance Parameters
Physical Features | |
Dimension(W×H×D) | 196×80×62mm |
Power dissipation | 11W |
Memory Features | |
Program memory | 24KB+48KB |
Data memory | 10KB+100KB |
General Features | |
Timers total 1ms 10ms 100ms |
256 4 16 236 |
Counters total | 256 |
Internal memory bits | 256 |
Stored permanently on power down | Data permanent stored |
Sequential control relay (S) | 256 |
Time Interrupts | 2 with 1ms resolution |
Edge Interrupts | 4 rising edges and/ or 4 falling edges |
Analog adjustment | Non |
Boolean execution speed | ≤0.15µs |
Float execution speed | ≤8µs |
Clock | embedded ,precision ±120s/m |
BD expansion board interface number | 1,Support CAN expansion board, analog expansion board |
System indicator | 5,STOP,RUN,SF,RMC,LINK/ACT |
RUN/STOP dial code | Yes,2 |
Battery card interface | Support,power supply below 2V,alarm bit SM195.0 |
Programming card and Memory card | Support |
Rated input voltage | 85-264VDC(47-63HZ) |
Power supply Native and extended bus+5V +24V |
1000mA 400mA |
Integrated Communication Function | |
Communication Interface | 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT0:PPI/Free port,RS485 After plugging in and restarting the RS485 board, PORT0 is fixed as PPI0 non-switchable and free-port FP0 is configured to the RS485 board. |
PPI baud rates(baud) | 9.6k,19.2k and 187.5k |
Freeport baud rates(baud) | 1.2k ~ 115.2k |
Maximum number of sations | 32 stations per segment,126 stations per network |
Maximum number of masters | 32 |
Point-to-point (PPI master station mode) | Yes(NETR/NETW), maximum 8 connections, and each connection has a maximum communication of 200 bytes |
MPI connect | (1PG/1OP) 8 in total, 2 reserved |
Maximum cable length Isolated repeater applied Isolated repeater unapplied |
When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50m |
Ethernet Function | |
Communication port | 1 Ethernet port |
Communication standard | IEEE802.3 standard |
Communication speed | 10Mbps and 100Mbps self-adaption |
Adaptive cross connection | Non support |
Interface to industrial Ethernet(10/100Mbps) | RJ45 port |
Protocol type | UDP/TCP protocol Support PDP_PPI, MODBUS_TCP, Socket, S7 protocols, support PLC Ethernet communication, support MiCo Ethernet programming. |
Collocation method | Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. |
Application interface | Support MiCo service, UDP_PPI, Modbus_TCP, S7 protocol, Socket programming.Support Ethernet port online firmware upgrade function. |
Maximum number of connections | 8 UDP_PPI, no master or slave 8 Modbus_TCP, no master or slave 4 Socket connections, 2 UDP, 2 TCP 8 S7 protocol, no master and slave, COTRUST PLC only as slave station |
User data number | Up to 200 bytes for UDP_PPI transmission. Up to 240 bytes are used for ModBus_TCP transmission. A maximum of 512 bytes is used for Socket transmission Up to 200 bytes for S7 transmission |
Port | local:1~65535 remote server:8888 |
Boot time or restart time after reset | 3 seconds |
Indicator lamp | Green RMC indicator: on: remote control in effect, off: remote control out Green Ethernet indicator: on: connection, flicker: transmission; out: not connected |
Maximum cable length | 100m |
Isolation | Communication port isolation |
Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB |
|||||||||||||
Communication Interface |
1(8 Pin) |
||||||||||||
Communication speed (kbps) |
1000 |
800 |
500 |
250 |
150 |
50 |
20 |
||||||
Maximum cable length(m) |
25 |
50 |
100 |
250 |
500 |
1000 |
2500 |
||||||
Maximum station address quantity |
127 |
||||||||||||
Station address range |
1-127 |
||||||||||||
Maximum number of master stations connect to slave stations |
32 |
||||||||||||
Collocation method |
CAN configuration blocks and EDS files |
||||||||||||
Maximum digital access |
Nomal IO |
CANopen IO |
|||||||||||
Byte |
Memory starting address |
Byte |
Memory starting address |
||||||||||
Input |
16 |
IB0 |
Input |
64 |
IB16 |
||||||||
Output |
16 |
QB0 |
Output |
64 |
QB16 |
||||||||
Maximum analog access |
Nomal IO |
CANopen IO |
|||||||||||
Channel |
Memory starting address |
channel |
Memory starting address |
||||||||||
Input |
32 |
AIW0 |
Input |
162 |
AIW64 |
||||||||
Output |
32 |
AQW0 |
Output |
162 |
AQW64 |
||||||||
Integrated Communication Function (CANopen) - use for CAN communication board model CTH2-CAN-01S2-EB |
|||||||||||||
Protocol |
CanFree |
||||||||||||
Use method |
Supported by internal library instructions |
I/O Features | |
Number of integrated digital inputs | 24 |
Input type | Sink/Source |
Number of integrated digital outputs | 16 |
Output type | Relay,dry contact |
Digital I/O mapping domain | 640DI/640DQ |
Analog I/O mapping domain | 194AI/194AQ |
Maximum number of expandable I/O module | 7 |
Maximum digital I/O configuration | 128DI/128DO |
Maximum analog I/O configuration | 32AI/32AQ |
Pulse catch inputs | 24 |
High-speed counters Total Uniphase counters Bi-phase counters |
6 6×30KHz 4×20KHz |
Digital Input Features | |
Number of integrated digital input | 24 |
Input type | Sink/ Source |
Rated voltage | 24V DC |
Maximum continuous permissible voltage | 30V DC |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum) |
15 VDC,2.5mA 5 VDC,1mA |
Isolation(field side to logical circuit) | 500V AC,1min |
Simultaneous input | 24 |
Maximum cable length Shielded Unshielded |
500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) |
Digital Output Features | |
Number of integrated digital output | 16 |
Output type | Solid-MOSFET,source |
Rated voltage | - |
Output voltage range | - |
Logical 1 Signal (minimum) | - |
Logical 0 Signal (Maximum) | - |
Rated current per point | 2A |
Rated current for each common point | |
Leakage current (maximum) | - |
Surge current(Maximum) | 7A |
Lamp load (maximum) | 30W DC/200W AC |
On resistance (contact) | 0.2Ω |
Isolation(field side to logical circuit) |
- |
Delay | Off to on:- on to off:- |
Contact life at rated load | 100000 times on and off |
Simultaneous input | All output point |
Parallel output | Only when the outputs are in the same group |
Maximum cable length Shielded Unshielded |
500m 150m |
* Support new V2 programming card
* Ultracapacitors power-off protection time 10 hours and extended batteries for 200 days
* Alarm function for insufficient battery power of the battery card: when it is lower than 2V, the alarm bit SM195.0
RS485 communication port definition
Connector |
PIN |
PORT0(RS485) |
FPORT0(RS485) |
|
1 |
Shell Grounded |
Shell Grounded |
2 |
+24V Grounded |
+24V Grounded |
|
3 |
RS485+signal B |
RS485+signal B |
|
4 |
Send the application |
Send the application |
|
5 |
+5V Grounded |
+5V Grounded |
|
6 |
+5V,100Ω |
+5V,100Ω |
|
7 |
+24V |
+24V |
|
8 |
RS485-signal A |
RS485-signal A |
|
9 |
NC |
NC |
|
shell |
Shell Grounded |
Shell Grounded |
RS485 expansion board communication interface
Module interface and connector |
PIN |
FPORT0(RS485) |
Note:when terminal resistors are needed, |
1 |
RS485+signal B |
2 |
RS485-signalA |
|
3 |
Terminal resistance |
|
4 |
Shell Grounded |
|
5 |
RS485 signal GND |
|
6 |
NC |
|
7 |
NC |
|
8 |
NC |
|
9 |
NC |
Suppliers with verified business licenses