Task: | Adjust |
---|---|
Structure: | Combination |
Mathematical Model: | Linear |
Signal: | 4-20ma HART RTD |
Function: | Automatic Control, Protection, Monitoring, Measurement |
Certification: | ISO: 9001, CE, CMMI5 |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
·8-Channel Analog Input |
·16-bit High Precision Sampling |
·Support Pt100, Cu50 and Software Configuration |
·Channels Isolated from the System |
Name of Parameter | Parameter Index |
|||
Number of Channels
|
8
|
|||
Power Consumption
|
<3W
|
|||
Isolation Type
|
Isolation Between Channels and the System
|
|||
Signal Type
|
Pt100,Cu50
Pt100:-148ºC~850ºC Cu50:-50ºC~150ºC |
|||
Input Switching
|
Each Channel can be set up Independently
|
|||
Precision
|
1ºC F.S.
|
|||
Input Resolution
|
0.1ºC
|
|||
Affect by Temperature
|
± 40ppm/ºC
|
|||
Input Resistance
|
Power on
|
2MΩ
|
||
Power off
|
>10MΩ
|
|||
Sample Period
|
Anti- industrial Electric
Frequency Resistance
|
e
400ms
|
||
Value of Pressure
Endurance
|
Site to Logic
|
500VAC/1min
|
||
CMRR
|
>120dB
|
|||
disconnection detection period
|
same to its sample period
|
|||
Length of Cable(Max.)
|
Distance of 100m to Transducer(including the Length of
Module and Terminal Board)
|